| Plan Review Notes For Permit 01080701 |
| Permit Number |
01080701 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-07 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | 2.NO COMBUSTIBLES ABOVE THE CEILING | | | IN THE RETURN AIR PLENUM. | | | 1997 SMC 609.1.1 | | | | | | 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS. 1997 SMC | | | 406.1 AND NFPA 90A 4-4.4.3. | | | | | | 4.AIR FROM THE RESTROOMS SHALL NOT BE | | | RECIRCULATED AS PER 1997 SMC 503.3.1 | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|