Plan Review Notes
Plan Review Notes For Permit 01080701
Permit Number 01080701
Review Stop M
Sequence Number 1
Notes
Date Text
2001-09-07 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
  
 1.OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
  
 2.NO COMBUSTIBLES ABOVE THE CEILING
 IN THE RETURN AIR PLENUM.
 1997 SMC 609.1.1
  
 3.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS. 1997 SMC
 406.1 AND NFPA 90A 4-4.4.3.
  
 4.AIR FROM THE RESTROOMS SHALL NOT BE
 RECIRCULATED AS PER 1997 SMC 503.3.1
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.