| 2001-08-28 00:00:00 | ***************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT COVER SHEET |
| | SHOWS ELECTRICAL UNDER THE "96" NEC. |
| | PLEASE NOTE WE ARE UNDER "99" NEC. |
| | PLEASE CORRECT. |
| | |
| | 2)NOTE: PLEASE ALSO NOTE THAT PER |
| | CITY OF WEST PALM BEACH LOCAL AMENDMENTS |
| | 210-50. OUTLET SPACING TO MEET LOCAL |
| | CODE. EVERY 20'FT OF UNENCUMBERED WALL |
| | SPACE. |
| | |
| | 3)NOTE: PLEASE NOTE THAT LOADS FOR TRACK |
| | LIGHTING NEEDS TO BE SHOWN PER 220-12B. |
| | |
| | 4)NOTE: PLEASE CLARIFY THAT ALL |
| | ELECTRICAL SHOWN ON SINGLE LINE DIAGRAM |
| | IS EXISTING. PANELS SHOWN AS EXISTING, |
| | WHAT ABOUT WIRE? PLEASE NOTE THAT THE |
| | TAPPED CONDUCTOR FROM DISCONNECT WITH |
| | 200A OCP FOR #3. THIS IS OK BUT, #3 |
| | NEEDS TO TERMINATE IN A PANEL WITH OCP |
| | THAT LIMITS LOAD TO 100AMPS. PLEASE |
| | NOTE THAT PANEL IS SHOWN WITH BUS ONLY?? |
| | PLEASE NOTE THAT THE #3`S ARE RATED FOR |
| | 100A PER 310-16 AND ALSO TERMINATE IN |
| | A 125A MCB PANEL"A"?? PLEASE NOTE THAT |
| | TAPPED CONDUCTORS NEED TO MEET ART: |
| | 240-21 FOR 10' AND 25'. |
| | |
| | 5)NOTE: PLEASE NOTE THAT PANEL "B " |
| | NEEDS TO BE SHOWN ON PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |