Plan Review Notes
Plan Review Notes For Permit 01080701
Permit Number 01080701
Review Stop E
Sequence Number 1
Notes
Date Text
2001-08-28 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT COVER SHEET
 SHOWS ELECTRICAL UNDER THE "96" NEC.
 PLEASE NOTE WE ARE UNDER "99" NEC.
 PLEASE CORRECT.
  
 2)NOTE: PLEASE ALSO NOTE THAT PER
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS
 210-50. OUTLET SPACING TO MEET LOCAL
 CODE. EVERY 20'FT OF UNENCUMBERED WALL
 SPACE.
  
 3)NOTE: PLEASE NOTE THAT LOADS FOR TRACK
 LIGHTING NEEDS TO BE SHOWN PER 220-12B.
  
 4)NOTE: PLEASE CLARIFY THAT ALL
 ELECTRICAL SHOWN ON SINGLE LINE DIAGRAM
 IS EXISTING. PANELS SHOWN AS EXISTING,
 WHAT ABOUT WIRE? PLEASE NOTE THAT THE
 TAPPED CONDUCTOR FROM DISCONNECT WITH
 200A OCP FOR #3. THIS IS OK BUT, #3
 NEEDS TO TERMINATE IN A PANEL WITH OCP
 THAT LIMITS LOAD TO 100AMPS. PLEASE
 NOTE THAT PANEL IS SHOWN WITH BUS ONLY??
 PLEASE NOTE THAT THE #3`S ARE RATED FOR
 100A PER 310-16 AND ALSO TERMINATE IN
 A 125A MCB PANEL"A"?? PLEASE NOTE THAT
 TAPPED CONDUCTORS NEED TO MEET ART:
 240-21 FOR 10' AND 25'.
  
 5)NOTE: PLEASE NOTE THAT PANEL "B "
 NEEDS TO BE SHOWN ON PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372