| Plan Review Notes For Permit 01080695 |
| Permit Number |
01080695 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-10-24 00:00:00 | ******************PROVISO*************** | | | | | | | | | OUTSIDE AIR CALCULATIONS INDICATE 4 | | | EMPLOYEES AND ONLY 2 CUSTOMERS (PLAN | | | A-5). | | | PLAN SHEET A-1 INDICATES 11 SEATS, O.A. | | | SHALL BE ADJUSTED FOR THE AMOUNT OF | | | PEOPLE...ALSO AIR BALANCE SCHEDULE | | | INDICATES A DEFICIT OF 480 CFM PUTTING | | | THE WHOLE BUILDING INTO A NEGATIVE | | | PRESSURE.FLORIDA ENERGY CODE | | | 409.1.ABCD., NOT TO EXCEED .02" W.G. | | | RELATIVE TO ALL INDOOR SPACES. |
|