Notes
Date Text
2001-08-31 00:00:00DENIED
  
 REFERENCES: - SPC-94 - SGC-97 - FACBC-97
  
 1) PLANS SHALL BE ROUTED TO DEPT. OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL. COUNTY WIDE AMENDMENTS TO SPC
 SECT. 101.4.7.
  
 2) SEPARATE GAS PERMIT REQUIRED. SEE
 ATTACHED SHEET FOR INFORMATION REQUIRED
 NOT ON PAGE A4.
  
 3) PAGE A1 TOTAL SQ. FT 1000. MINUS 200
 FT FOR RESTROOM AND ACCESSABLE ROUTE =
 800 SQ FT. 800 SQ FT REQUIRES 1 EACH
 WATER CLOSET AND 1 LAV FOR MEN AND WOMEN
 SPC-94 TABLE 407.
  
 4) PAGE A4 SANITARY AND GREASE RISER
 DIAGRAMS, 2 WAY CLEAN OUTS ARE REQUIRED
 WITH-IN 5' OF EXITING BUILDING. SPC-94
 SECT. 710.2.1(6) AND 710.2.2.
  
 5) PAGE A4, WATER RISER, SHOW SHUT OFF
 VALVE AT WATER HEATER SUPPLY. SECT 501.6
  
 6) PAGE A4, WATER RISER DIAGRAM, MAXIMUM
 FIXTURES 1/2" COLD IS 2 AND MAXIMUM FIX-
 TURES ON 1/2" HOT IS 4. (SEE HAND SINK,
 WOKS, AND STEAM TABLE) COUNTYWIDE AMEND-
 MENTS TO SPC-94 SECT. 607.7.
  
 7) PAGE A4, WATER RISER DIAGRAM, HOT &
 COLD LINES ARE CROSSED TO HAND SINK, WOK
 AND STEAM TABLE.
  
 8) PAGE A4, GAS RISER DIAGRAM, MANUAL
 SHUT OFF VALVES TO BE UPSTREAM FROM
 UNION (INLET), AND DOWNSTREAM FORM UNION
 (OUTLET), AT THE EMERGENCY SOLENOID
 VALVE.
  
 9) PAGE A4, GAS RISER DIAGRAM/SLAB GAS
 DETAIL, ONE SHOWS GAS TO STEAM TABLE TO
 RUN OVERHEAD, AND THE OTHER SHOWS IN IN
 THE SLAB. PLEASE CLAIRFY.
  
 10) PAGE A4, WATER RISER DIAGRAM, BACK-
 FLOW REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377