| 2001-08-31 00:00:00 | DENIED |
| | |
| | REFERENCES: - SPC-94 - SGC-97 - FACBC-97 |
| | |
| | 1) PLANS SHALL BE ROUTED TO DEPT. OF |
| | BUSINESS REGULATION FOR REVIEW AND |
| | APPROVAL. COUNTY WIDE AMENDMENTS TO SPC |
| | SECT. 101.4.7. |
| | |
| | 2) SEPARATE GAS PERMIT REQUIRED. SEE |
| | ATTACHED SHEET FOR INFORMATION REQUIRED |
| | NOT ON PAGE A4. |
| | |
| | 3) PAGE A1 TOTAL SQ. FT 1000. MINUS 200 |
| | FT FOR RESTROOM AND ACCESSABLE ROUTE = |
| | 800 SQ FT. 800 SQ FT REQUIRES 1 EACH |
| | WATER CLOSET AND 1 LAV FOR MEN AND WOMEN |
| | SPC-94 TABLE 407. |
| | |
| | 4) PAGE A4 SANITARY AND GREASE RISER |
| | DIAGRAMS, 2 WAY CLEAN OUTS ARE REQUIRED |
| | WITH-IN 5' OF EXITING BUILDING. SPC-94 |
| | SECT. 710.2.1(6) AND 710.2.2. |
| | |
| | 5) PAGE A4, WATER RISER, SHOW SHUT OFF |
| | VALVE AT WATER HEATER SUPPLY. SECT 501.6 |
| | |
| | 6) PAGE A4, WATER RISER DIAGRAM, MAXIMUM |
| | FIXTURES 1/2" COLD IS 2 AND MAXIMUM FIX- |
| | TURES ON 1/2" HOT IS 4. (SEE HAND SINK, |
| | WOKS, AND STEAM TABLE) COUNTYWIDE AMEND- |
| | MENTS TO SPC-94 SECT. 607.7. |
| | |
| | 7) PAGE A4, WATER RISER DIAGRAM, HOT & |
| | COLD LINES ARE CROSSED TO HAND SINK, WOK |
| | AND STEAM TABLE. |
| | |
| | 8) PAGE A4, GAS RISER DIAGRAM, MANUAL |
| | SHUT OFF VALVES TO BE UPSTREAM FROM |
| | UNION (INLET), AND DOWNSTREAM FORM UNION |
| | (OUTLET), AT THE EMERGENCY SOLENOID |
| | VALVE. |
| | |
| | 9) PAGE A4, GAS RISER DIAGRAM/SLAB GAS |
| | DETAIL, ONE SHOWS GAS TO STEAM TABLE TO |
| | RUN OVERHEAD, AND THE OTHER SHOWS IN IN |
| | THE SLAB. PLEASE CLAIRFY. |
| | |
| | 10) PAGE A4, WATER RISER DIAGRAM, BACK- |
| | FLOW REQUIRED. |
| | |