Notes
Date Text
2001-08-21 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 PLEASE NOTE, NEED RATING FOR MAIN DISC-
 -ONNECT.
  
 2)NOTE: PLEASE PROVIDE CLARIFICATION FOR
 EQUIPMENT GROUNDING CONDUCTOR BETWEEM
 MAIN AND PANEL. 250-122
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372