| Plan Review Notes For Permit 01080695 |
| Permit Number |
01080695 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-21 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE, NEED RATING FOR MAIN DISC- | | | -ONNECT. | | | | | | 2)NOTE: PLEASE PROVIDE CLARIFICATION FOR | | | EQUIPMENT GROUNDING CONDUCTOR BETWEEM | | | MAIN AND PANEL. 250-122 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELELCTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|