| Plan Review Notes For Permit 01080677 |
| Permit Number |
01080677 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-16 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE SUBMIT THE FOLLOWING INFORMATION | | | FOR REVIEW: | | | | | | | | | 1.INDICATE RETURN AIR LOCATION AND | | | GRILL SIZE ON PLAN. | | | | | | 2.INDICATE GRILL SIZE FOR SUPPLY DROPS | | | UPSTAIRS. | | | | | | 3.CLARIFY LOCATION OF AHU, CLOSET OR | | | ATTIC.SHOULD AHU BE LOCATED IN THE | | | ATTIC, SHALL COMPLY WITH 1997 SMC | | | 304.4.1 OPENING NO LESS THAN 22" X | | | 36".ALSO AMENDED 1997 SMC 304.4.2, | | | SHALL HAVE A CONVIENCE OUTLET AND | | | A LIGHT ON THE SERVICE SIDE OF THE | | | EQUIPMENT CONTROLLED BY A SWITCH | | | AT THE ACCESS OPENING. | | | | | | 4.INDICATE LINE SIZE OF LIQUID, | | | SUCTION AND CONDENSATE. | | | | | | 5.LIST MATERIAL FOR CONDENSATE AND | | | TERMINATION. | | | | | | 6.PLEASE INDICATE MATERIAL AND R VALUE | | | OF DUCTWORK. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|