| Plan Review Notes For Permit 01080628 |
| Permit Number |
01080628 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-10-22 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT NOW JUST THE | | | TWO SETS OF PLANS ARE BEING SUBMITTED | | | FOR REVIEW. | | | PLEASE NOTE THAT FEED GOING TO GUTTER | | | THAT FEEDS DISC "DS" AND PANEL "3MA" | | | DOESN'T SHOW ANY MAIN FEEDING THIS? | | | PLEASE CALRFIY? TAPPED CONDUCTORS? | | | NOTHING SHOWN FOR "MDP" SCHEDULE FEEDING | | | THIS EQUIPMENT? OCP?. PLEASE NOTE TAPS | | | PER 240-21. | | | | | | 2)NOTE: PLEASE NOTE THAT NOTE FROM FIRST | | | TWO REVIEWS, PLEASE CLARIFY IF REVISED | | | LOADS SHOWN ARE AT THE 125% ?? | | | PLEASE CALRIFY. | | | | | | 3)NOTE: PLEASE CLARIFY WHERE DISC "DS" | | | IS BEING FED FROM? PLEASE NOTE THAT LOAD | | | SHOWN FOR PANEL "3MA" IS AT 336AMPS, | | | PLEASE NOTE THAT PANEL SCHEDULE FOR 3MA | | | DOESN'TSHOW FEEDING DISC "DS"? | | | FEEDERS GOINGTO GUTTER ARE RATED FOR | | | 380AMPS? PLEASE CLARIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|