2001-10-22 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THAT NOW JUST THE
 TWO SETS OF PLANS ARE BEING SUBMITTED
 FOR REVIEW.
 PLEASE NOTE THAT FEED GOING TO GUTTER
 THAT FEEDS DISC "DS" AND PANEL "3MA"
 DOESN'T SHOW ANY MAIN FEEDING THIS?
 PLEASE CALRFIY? TAPPED CONDUCTORS?
 NOTHING SHOWN FOR "MDP" SCHEDULE FEEDING
 THIS EQUIPMENT? OCP?. PLEASE NOTE TAPS
 PER 240-21.
  
 2)NOTE: PLEASE NOTE THAT NOTE FROM FIRST
 TWO REVIEWS, PLEASE CLARIFY IF REVISED
 LOADS SHOWN ARE AT THE 125% ??
 PLEASE CALRIFY.
  
 3)NOTE: PLEASE CLARIFY WHERE DISC "DS"
 IS BEING FED FROM? PLEASE NOTE THAT LOAD
 SHOWN FOR PANEL "3MA" IS AT 336AMPS,
 PLEASE NOTE THAT PANEL SCHEDULE FOR 3MA
 DOESN'TSHOW FEEDING DISC "DS"?
 FEEDERS GOINGTO GUTTER ARE RATED FOR
 380AMPS? PLEASE CLARIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372