| Plan Review Notes For Permit 01080628 |
| Permit Number |
01080628 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-10 00:00:00 | ************* UNSAT ************* | | | | | | PLEASE NOTE THAT NOTE FROM FIRST REVIEW | | | NEEDS TO BE SHOWN.? ALL CONTINUOUS LOADS | | | AT 125%. PER 230-42/215-2/3 | | | | | | | | | 1)NOTE: PLEASE ALSO NOTE THAT FOUR | | | DIFFERENT SETS OF PLANS WERE SUBMITTED | | | SHOW DIFF LIGHTING AND FLOOOR PLANS | | | AND DATED AS NEW PLANS? PLEASE ALSO | | | NOTE THAT COMPLETELY REVISED RISER | | | DIAGRAMS WERE SUBMITTED W/ OLD FLOOR | | | PLANS???? YET NEW FLOOR PLANS ARE WITH | | | OLD RISER DIAGRAM WITH REVISED SIGNED | | | AND SEALED BY ENGINEER OF RECORD?????? | | | | | | | | | PLEASE SUBMIT TWO SETS OF PLANS FOR | | | REVIEW AND TAKE OLD ELECTRICAL OUT? | | | IT IS NOT CLEAR WHICH ONES THEY ARE? | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | 2)NOTE: PLEASE SUBMIT PANEL (MDP ) | | | SCHEDULE. PLEASE CLARIFY IF MDP HAS ONE | | | MAIN ? | | | SIZE OF EXISTING MDP? OCP | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|