| Plan Review Notes For Permit 01080628 |
| Permit Number |
01080628 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-09-07 00:00:00 | *******************DENIED*************** | | | | | | | | | PLEASE PROVIDE THE FOLLOWING INFORMATION | | | FOR REVIEW. | | | | | | | | | 1.OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-1989. | | | | | | 2.AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. | | | | | | 3.NO COMBUSTIBLES ABOVE THE CEILING | | | IN THE RETURN AIR PLENUM. | | | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | AS REQUIRED AS PER 1997 SMC 406.1. | | | | | | 5.NOTIFICATION TO ALARM/STROBE AS PER | | | NFPA 90A 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|