| Plan Review Notes For Permit 01080613 |
| Permit Number |
01080613 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2001-12-05 00:00:00 | **************** UNSAT *********** | | | | | | 1)NOTE: PLEASE SUBMIT A COMNPLETE SET | | | OF ELECTRICAL PLANS BY THE ARCH/ENG OF | | | RECORD. A REVISION WAS SUBMITTED BY | | | THE ELECTRICAL CONTRACTOR LESS THAN A | | | WEEK AGO SHOWING A COMPLETELY DIFERENT | | | ELECTRICALSERVICE. | | | | | | 2)NOTE: PLEASE NOTE THAT NEW SERVICE | | | SHOWN FOR LAUNDRY ALONG IS NOT PERMITTED | | | UNLESS THERE IS A TWO HOUR SEPARATION | | | BETWEEN EXISTING AND NEW. | | | | | | 3)NOTE: PLEASE NOTE GROUPING OF DISC`S | | | 230-72 | | | | | | | | | PLEASE SUBMIT NEW PLANS SHOWING COMPLETE | | | ELECTRICAL. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|