| Plan Review Notes For Permit 01080609 |
| Permit Number |
01080609 |
|
| Review Stop |
R |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2002-02-01 00:00:00 | TRUSSES DENIED | | | | | | 1) SUBMIT REVISED PLANS AND CONNECTOR | | | SCHEDULE AS INDICATED IN LETTER FROM | | | THE ENGINEER. | | | | | | 2) TRUSS DRAWINGS CONTAIN INCORRECT | | | DESIGN INFORMATION. IF TRUSSES ARE | | | DESIGNED USING ASCE 7-95 THE CORRECT | | | WIND SPEED TO USE IS 140 MPH. SEE MAP IN | | | ASCE 7-95. IF USING 110 MPH WIND SPEED | | | USE 1997 SBC SECTION 1606. | | | | | | 3) PROVIDE ENGINEERED DRAWINGS OF THE | | | REPAIRS TO THE TRUSSES WITH DEFLECTIONS | | | GREATER THAN L/360, AS INDICATED IN THE | | | LETTER FROM MR. AVERKAMP. | | | | | | 4) PROVIDE THE TRUSS LAYOUT AND DRAWINGS | | | TO THE DESIGNER OF RECORD FOR THE | | | STRUCTURE FOR HIS REVIEW AND APPROVAL. | | | THE DESIGNER OF RECORD OF THE STRUCTURE | | | IS TO ACKNOWLEDGE HIS APPROVAL WITH HIS | | | SIGNATURE AND DATE ON THE LAYOUT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|