| Plan Review Notes For Permit 01080557 |
| Permit Number |
01080557 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-12-04 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) PER PREVIOUS PLAN REVIEW 11-13-01, | | | NEW PLANS SUBMITTED SHALL HAVE PLAN RE- | | | VIEW AND STAMP FROM DEPT OF BUSINESS | | | HOTEL AND RESTURANTS ATTACHED TO THEM. | | | 2) PER PREVIOUS PLAN REVIEW 11-13-01, | | | URNALS SHALL COMPLY WITH FACBC 4.18. | | | 4.18.3 REQUIRES A MINIMUM 30"X48" CLEAR | | | FLOOR SPACE. SHT A-4 SHOWS 2'3-1/2", | | | SHTS A-1, A-2, & A-3 HAVE NO MEASURMENTS | | | 3) SHT A-4, DOOR SWINGS FOR DO6, & DO9 | | | REQUIRE EITHER NEW SIGNED AND SEALED | | | SHEETS OR BE INITILED AND DATED BY ARC- | | | HITECT OF RECORD. PER PREVIOUS REVIEW | | | 11-13-01. | | | 4) PER PREVIOUS REVIEW, GAS PERMIT | | | APPLICATION REQUIREMENT SHEET #9, SUBMIT | | | MANUFACTURE SHEETS FOR GAS EQUIPMENT PER | | | SGC-97 SECS 602 THRU 612. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|