| 2001-11-13 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 - SGC-97 |
| | |
| | 1) PLANS STAMPED BY DEPT OF BUSINESS AND |
| | PROFESSIONAL REGULATION ARE NOT THE SET |
| | BEING SUBMITTED FOR PLAN REVIEW. NO SEAL |
| | OR SIGNITURE ON THESE PLANS. |
| | 2) PAGE A-4 DETAIL A FOR URNAL DOES NOT |
| | SHOW CLEAR FLOOR SPACE AS REQUESTED. NO |
| | MEASUREMENT GIVEN, 30"X48" REQUIRED. |
| | 3) PAGE A-4, ROOMS DO6, DO7, DO8, & DO9 |
| | DOORS SHALL NOT SWING INTO CLEAR FLOOR |
| | SPACE OF FIXTURES OR TURNING RADIUS. DO7 |
| | AND DO8 WERE PENNED IN BUT ALL HAVE TO |
| | SWING OUT AND SHOULD NOT BE PENNED IN |
| | UNLESS CHANGES ARE SIGNED AND DATED. |
| | 4) PAGES P-1, 3 COMPARTMENT SINK IN FOOD |
| | PREP AREA DOES NOT REQUIRE TRAPS, IT |
| | SHALL DRAIN TO FLOOR SINK. |
| | 5) PAGE P-1, FUNNEL FLOOR DRAINS NOT |
| | APPROVED. ALL INDIRECT WASTE SHALL DRAIN |
| | TO FLOOR SINK. |
| | 6) PAGES P-1, & P-2 TWO WAY CLEAN OUTS |
| | ON BLDG DRAIN WHERE IT TIES INTO BLDG |
| | SEWER SHALL HAVE 2-WAY CLEAN OUTS. SHOW |
| | C/O'S ON PLANS PLEASE. SPC SEC 710.2.1 |
| | (6) & 710.2.2. |
| | 7) GAS PERMIT APPLICATION SHEET #'S 6 & |
| | 9 WHERE NOT ADDRESSED. PLEASE SUPPLY IN- |
| | FORMATION REQUESTED. |
| | 8) PAGE P-2 GAS ISOMETERIC RISER DIAGRAM |
| | REQUIRES A UNION BETWEEN MANUAL VALVE & |
| | SOLENOID VALVE FOR HOOD SHUT OFF. |
| | 9) CALCULATIONS FOR COMBUSTION AIR NOT |
| | ACCEPTABLE. DOOR TO HEATER ROOM CAN BE |
| | CLOSED AND LOCKED WHICH WOULD MAKE THE |
| | ROOM A CONFINED SPACE. |
| | |
| | REVIEW BY KEN STEVENS |