Plan Review Notes
Plan Review Notes For Permit 01080557
Permit Number 01080557
Review Stop P
Sequence Number 2
Notes
Date Text
2001-11-13 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 1) PLANS STAMPED BY DEPT OF BUSINESS AND
 PROFESSIONAL REGULATION ARE NOT THE SET
 BEING SUBMITTED FOR PLAN REVIEW. NO SEAL
 OR SIGNITURE ON THESE PLANS.
 2) PAGE A-4 DETAIL A FOR URNAL DOES NOT
 SHOW CLEAR FLOOR SPACE AS REQUESTED. NO
 MEASUREMENT GIVEN, 30"X48" REQUIRED.
 3) PAGE A-4, ROOMS DO6, DO7, DO8, & DO9
 DOORS SHALL NOT SWING INTO CLEAR FLOOR
 SPACE OF FIXTURES OR TURNING RADIUS. DO7
 AND DO8 WERE PENNED IN BUT ALL HAVE TO
 SWING OUT AND SHOULD NOT BE PENNED IN
 UNLESS CHANGES ARE SIGNED AND DATED.
 4) PAGES P-1, 3 COMPARTMENT SINK IN FOOD
 PREP AREA DOES NOT REQUIRE TRAPS, IT
 SHALL DRAIN TO FLOOR SINK.
 5) PAGE P-1, FUNNEL FLOOR DRAINS NOT
 APPROVED. ALL INDIRECT WASTE SHALL DRAIN
 TO FLOOR SINK.
 6) PAGES P-1, & P-2 TWO WAY CLEAN OUTS
 ON BLDG DRAIN WHERE IT TIES INTO BLDG
 SEWER SHALL HAVE 2-WAY CLEAN OUTS. SHOW
 C/O'S ON PLANS PLEASE. SPC SEC 710.2.1
 (6) & 710.2.2.
 7) GAS PERMIT APPLICATION SHEET #'S 6 &
 9 WHERE NOT ADDRESSED. PLEASE SUPPLY IN-
 FORMATION REQUESTED.
 8) PAGE P-2 GAS ISOMETERIC RISER DIAGRAM
 REQUIRES A UNION BETWEEN MANUAL VALVE &
 SOLENOID VALVE FOR HOOD SHUT OFF.
 9) CALCULATIONS FOR COMBUSTION AIR NOT
 ACCEPTABLE. DOOR TO HEATER ROOM CAN BE
 CLOSED AND LOCKED WHICH WOULD MAKE THE
 ROOM A CONFINED SPACE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377