| Notes |
| Date |
Text |
| 2001-11-20 00:00:00 | ******************PROVISO*************** | | | | | | | | | EXHAUST DUCT CONVEYING NOXIOUS GASES, | | | FLAMMABLE VAPORS, CORROSIVE VAPORS | | | SHALL TERMINATE OUTSIDE THE BUILDING | | | AND BE LOCATED 10 FT FROM ANY ADJACENT | | | BUILDING, PARKING AREA, ADJACENT | | | PROPERTY LINE, WINDOW, DOOR OR AIR | | | INTAKE OPENING. | | | | | | PLEASE NOTE - GREASE DUCT SHALL BE | | | INSPECTED PRIOR TO BEING ENCLOSED. | | | PROVIDE DETAIL OF SHAFT ENCLOSURE AND | | | TERMINATION OF GREASE DUCT WITH MECH | | | HOOD PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|