2001-11-20 00:00:00******************PROVISO***************
  
  
 EXHAUST DUCT CONVEYING NOXIOUS GASES,
 FLAMMABLE VAPORS, CORROSIVE VAPORS
 SHALL TERMINATE OUTSIDE THE BUILDING
 AND BE LOCATED 10 FT FROM ANY ADJACENT
 BUILDING, PARKING AREA, ADJACENT
 PROPERTY LINE, WINDOW, DOOR OR AIR
 INTAKE OPENING.
  
 PLEASE NOTE - GREASE DUCT SHALL BE
 INSPECTED PRIOR TO BEING ENCLOSED.
 PROVIDE DETAIL OF SHAFT ENCLOSURE AND
 TERMINATION OF GREASE DUCT WITH MECH
 HOOD PERMIT APPLICATION.
  