| 2001-11-20 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 01080557 |
| | 112 N DIXIE HWY |
| | BERET & BAGUETTE |
| | FRENCH BAKERY & COFFEE |
| | MARION CONSTRUCTION |
| | TEL: 722-8472 |
| | SBC= 1997 STANDARD BUILDING CODE |
| | SBC*= AMENDMENTS/ STANDARD BUILDING CODE |
| | |
| | 1)- SHEET EX-1 RE: CAPPING & SCUPPERS, |
| | SHOW COMPLIANCE WITH 1517.6.4. |
| | A) SHOW CALCULATIONS FOR THE ROOF DRAIN |
| | AGE AS PER THE STANDAARD PLUMBING CODE. |
| | CHAPTER 11. |
| | B) PLANS ARE NOT CLEAR AS TO WHAT IS |
| | SCUPPRS FOR ROOF DRAINAGE AND WHICH ARE |
| | EMERGENCY OVERFLOW SCUPPERS, WHICH ARE |
| | BEING DELETED? SHOW CODE COMPLIANCE. |
| | FROM PREVIOUS PLAN REVIEW. |
| | |
| | 2)- SHEET A-5 INDICATES THE USE OF PT |
| | WOOD ON THE EXTERIOR OF THE BUILDING. |
| | SBC F 102.2.1. / EXTERIOR WALLS OF BUILD |
| | INGS LOCATED IN THE FIRE DISTRICT SHALL |
| | COMPLY WITH THE REQUIREMENTS IN TABLE |
| | 600." NO COMBUSTIBLES, NO TYPE VI CON- |
| | STRUCTION ALLOWED. |
| | |
| | 3)- NEW GLAZING INCLUDING THE SKYLIGHTS |
| | PRODUCT APPROVAL FOR ALL GLAZED OPENINGS |
| | ARE REQUIRED(2 COPIES) SBCCI OR DADE |
| | COUNTY PRODUCT TESTING REPORTS ARE |
| | REQUIRED. LARGE MISSLE IMPACT RESISTANCE |
| | TESTING WILL BE REQUIRED.SBC 1606.4.1*/ |
| | SBC 1707.4.1*.PREVIOUS REVIEW. |
| | |
| | 4)- SHEET A-5 INDICATES A NEW GLASS |
| | DOOR, SIDELITE & TRANSOM, MISSING PRO- |
| | DUCT TESTING REPORT EITHER SBCCI OR DADE |
| | COUNTY ARE ACCEPTED.SBC 1606.4.1.*/ |
| | SBC1707.4..1.*. |
| | |
| | 5)- REVISION DATES ARE NOT REVISED ON |
| | THE LATEST DRAWINGS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561) 659-8096 X 8412 |