2001-11-20 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01080557
 112 N DIXIE HWY
 BERET & BAGUETTE
 FRENCH BAKERY & COFFEE
 MARION CONSTRUCTION
 TEL: 722-8472
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS/ STANDARD BUILDING CODE
  
 1)- SHEET EX-1 RE: CAPPING & SCUPPERS,
 SHOW COMPLIANCE WITH 1517.6.4.
 A) SHOW CALCULATIONS FOR THE ROOF DRAIN
 AGE AS PER THE STANDAARD PLUMBING CODE.
 CHAPTER 11.
 B) PLANS ARE NOT CLEAR AS TO WHAT IS
 SCUPPRS FOR ROOF DRAINAGE AND WHICH ARE
 EMERGENCY OVERFLOW SCUPPERS, WHICH ARE
 BEING DELETED? SHOW CODE COMPLIANCE.
 FROM PREVIOUS PLAN REVIEW.
  
 2)- SHEET A-5 INDICATES THE USE OF PT
 WOOD ON THE EXTERIOR OF THE BUILDING.
 SBC F 102.2.1. / EXTERIOR WALLS OF BUILD
 INGS LOCATED IN THE FIRE DISTRICT SHALL
 COMPLY WITH THE REQUIREMENTS IN TABLE
 600." NO COMBUSTIBLES, NO TYPE VI CON-
 STRUCTION ALLOWED.
  
 3)- NEW GLAZING INCLUDING THE SKYLIGHTS
 PRODUCT APPROVAL FOR ALL GLAZED OPENINGS
 ARE REQUIRED(2 COPIES) SBCCI OR DADE
 COUNTY PRODUCT TESTING REPORTS ARE
 REQUIRED. LARGE MISSLE IMPACT RESISTANCE
 TESTING WILL BE REQUIRED.SBC 1606.4.1*/
 SBC 1707.4.1*.PREVIOUS REVIEW.
  
 4)- SHEET A-5 INDICATES A NEW GLASS
 DOOR, SIDELITE & TRANSOM, MISSING PRO-
 DUCT TESTING REPORT EITHER SBCCI OR DADE
 COUNTY ARE ACCEPTED.SBC 1606.4.1.*/
 SBC1707.4..1.*.
  
 5)- REVISION DATES ARE NOT REVISED ON
 THE LATEST DRAWINGS.
  
 BUILDING PLAN REVIEW