Plan Review Notes
Plan Review Notes For Permit 01080557
Permit Number 01080557
Review Stop P
Sequence Number 1
Notes
Date Text
2001-08-29 00:00:00DENIED
  
 REFERENCE SPC-94/SGC-97/FACBC-97
  
 1) PLANS SHALL BE ROUTED TO DEPT. OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL. COUNTYWIDE AMENDMENTS TO SPC
 SEC. 101.4.7.
 2) PAGE A-4, DETAIL A/A-4, URNAL MUST
 COMPLY WITH FACBC-97 SECTION 4.18
 CLEAR FLOOR SPACE AND TYPE OF URNAL AND
 URNAL HEIGTH ECT.
 3) PAGE A-4, DETAIL G/A-4, W/C TO BE 1'-
 6" OFF WALL. PER FACBC-97 SECTION 4.16.
 4) PAGE A-4, ROOMS DO6-DO7-DO8-DO9,
 DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACE OF ANY FIXTURE. FACBC-97
 SECTION 4.17.5.
 5) PAGE P-1, 3 COMPARTMENT SINKS FOR
 DISHWASHING SHALL HAVE A TRAP FOR EACH
 COMPARTMENT. SPC-94, SECTION 1001.8.1
 6) PAGES P-1 & P-2, SAFE WASTES NOT AL-
 LOWED. FLOOR SINKS ARE REQUIRED FOR ALL
 INDIRECT WASTE. SPC-94 SECTIONS 804.1 &
 807.
 7) PAGES P-1 & P-2, 3 COMPARTMENT SINK
 IN FOOD PREPARATION AREA TO DRAIN IN-
 DIRECTLY TO A FLOOR SINK. SPC-94 SECTION
 804.
 8) PAGE P-1, GREASE TRAP TO BE SIZED AND
 LOCATED BY THE CITY UTILITY DEPT. PLEASE
 CONTACT RODNEY COMPO, (561) 837-4074.
 SEE ATTACHED SHEET FOR WPB CITY UTILITY
 APPROVED GREASE TRAP DETAIL.
 9) PAGE P-1, HUB DRAINS NOT ALLOWED. ALL
 INDIRECT WASTE TO FLOOR SINK. SPC-94
 SECTION 804.5.
 10) PAGES P-1 & P-2, ICE MACHINE TO
 DRAIN TO FLOOR SINK NOT FLOOR DRAIN.
 SPC-94 SECTION 804.
 11) PAGE P-2, 2-WAY CLEAN-OUTS ARE REQ-
 UIRED WITH-IN 5' OF EXITING BLDG. SPC-94
 SECTIONS 710.2.1(6) & 710.2.2.
 12) SEPARATE PERMIT FOR GAS. SEE ATTACH-
 ED SHEET FOR GAS PERMIT APPLICATION RE-
 QUIREMENTS.
 13) PAGE P-2 GAS ISOMETRIC RISER DIAGRAM
 FOR GAS SOLENOID VALVE. SHOW DETAIL OF
 EMERGENCY SHUT-OFF VALVE. MANUAL VALVE
 SHALL BE UPSTREAM OF UNION FOR SERVICING
 SOLENOID VALVE.
 14) PAGES A-1, A-2, A-3, A-6, & P-1.
 SUBMIT COMBUSTION AIR CALCULATIONS FOR
 GAS WATER HEATER. SGC-97 SECTION 402.4.4
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377