| Plan Review Notes For Permit 01080557 |
| Permit Number |
01080557 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-28 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | PLEASE NOTE THAT AIC RATINGS WERE SHOWN | | | FOR PANELS BUT NOT FOR MAIN. | | | | | | 2) NOTE: PLEASE SHOW ALL CONTINUOUS AT | | | 125%. (LIGHTING ETC), PER 230-42 AND | | | 215-3 | | | | | | 3)NOTE: PLEASE NOTE THAT PLANS NEED TO | | | SHOW TRACK LIGHTING LOAD CALCULATIONS | | | PER 220-12B | | | | | | 4)NOTE: PLEASE NOTE THAT LOAD SHOWN FOR | | | EXISTING SERVICE IS AT 21KW AND LOAD | | | SHOWN FOR NEW SERVICE PUTS LOAD OVER | | | SERVICE ENTRANCE CONDUCTOR RATINGS. PER | | | 310-16 | | | PLEASE PROVIDE A ONE WEEK SIGNED AND | | | SEALED READ OUT FOR EXISTING SERVICE OR | | | A 12 MONTHS WORTH OF FPL STATEMENTS FOR | | | VERIFICATION OF LOAD. | | | | | | 5)NOTE: PLEASE ALSO PLACE NOTE ON PLANS | | | E-3 FOR LIGHTING FIX SCHEDULE. | | | "ALL FIXTURES AND COMPONENTS TO BE "UL" | | | LISTED". | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|