| Notes |
| Date |
Text |
| 2001-09-17 00:00:00 | SHEET EX-1 RE: CAPPING OF SCUPPERS. | | | ROOF DRAINAGE, INCLUDING EMERGENCY | | | OVERFLOWMUST BE MAINTAINED IN | | | ACCORDANCE WITH SBC 1517.6.4. | | | | | | THE NEW GLAZING INCLUDING THE SKYLIGHTS | | | MUST COMPLY WITH THE CITY'S HURRICANE | | | MISSILE IMPACT RESISTANCE REQUIREMENTS. | | | PLEASE PROVIDE SPECIFIC DETAILS. | | | | | | PROVIDE A RECENT SURVEY SO THAT | | | COMPLIANCE WITH SBC 3203 AND OTHER | | | ISSUES MAY BE DETERMINED. | | | | | | SHEET A5.THIS BUILDING IS LOCATED IN | | | THE DESIGNATED FIRE DISTRICT AND | | | COMBUSTIBLE CONSTRUCTION IS NOT | | | PERMITTED WITHIN OR ON THE OUTSIDE OF | | | EXTERIOR WALLS.SEE SBC F 102. | | | | | | PROVIDE A CLEAR SCOPE OF WORK TO BE | | | ACCOMPLISHED UNDER THIS PERMIT FOR THE | | | $150,000 VALUATION DIFFERNTIATING THAT | | | WHICH IS TO BE PERFORMED AT COST PLUS. | | | | | | SHEET A3.THE EXIT LIGHT SHOWN AT DOOR | | | D03 IS ILL PLACED.SEE SBC 1001.1.3. | | | IT WOULD SERVE BETTER ON THE KITCHEN | | | SIDE. |
|