| 2001-09-05 00:00:00 | SHEET A1 DOOR SCHEDULE, REMARKS, "RATED" | | | SHOW A SPECIFIC LABEL REQUIREMENT IN | | | ACCORDANCE WITH SBC 705.1.3SAME SHEET | | | A2 | | | | | | SHOW A LIFE SAFETY PLAN FOR THE 11TH | | | FLOOR TO INCLUDE THE OTHER PORTION OF | | | THE FLOOR. | | | | | | SHEET A2, THE TWO EXITS DO NOT MEET THE | | | 1/2 DIAGONAL DISTANCE SEPARATION | | | REQUIREMENTS OF SBC 1004.1.4. | | | | | | SHEET A2.EGRESS IS NOT PERMITTED | | | THROUGH STORAGE AREAS.SEE SBC | | | 1001.1.3. | | | | | | | | | THE DECLARED $180K VALUATION APPEARS TO | | | BE TOO LOW FOR THIS SCOPE OF WORK. | | | PLEASE PROVIDE A COPY OF THE SIGNED | | | CONTRACT AND DETAILED TAKEOFF TO VERIFY | | | THE SUM. |
|