| 2001-09-05 00:00:00 | APPROVED WITH PROVISO: |
| | 1-FLOOD ZONE A0. WILL NEED TO PROVIDE |
| | THE ELEVATION CERTIFICATE. |
| | 2-SURVEY SHOW TWO STORY TOWNHOUSE FOR |
| | LOT 123. REVISE AS REQUIRED. |
| | 3-REVISE THE DESIGN CERTIFICATION FOR |
| | BUILDING CODE COMPLIANCE FORM. |
| | -THE MEAN ROOF HEIGHT IS INCORRECT. |
| | MEAN ROOF HEIGHT IS TAKEN FROM THE |
| | FINISH GRADE, NOT FROM THE FIN. FL, |
| | TO THE AVERAGE POINT OF THE HIGHEST |
| | ROOF. THEREFORE, MEAN ROOF HEIGHT IS |
| | +/- 15'-6" SEE EXTERIOR ELEVATIONS. |
| | -ALSO, REVISE THE BASIC VELOCITY |
| | PRESSURE ACCORDINGLY. SEE TABLE |
| | 1606.2A SBC 1997. |
| | 4-ENERGY CALCULATIONS SHOW MULTIFAMILY |
| | FOR 5 UNITS. THIS BUILDING HAS ONLY |
| | THREE. REVISE AS REQUIRED. |
| | -ALSO REVISE THE #OF BEDROOMS ACOORDING |
| | TO THE OPTIONS SELECTED. |
| | 5-PROVIDE ACTUAL DADE COUNTY PRODUCT |
| | APPROVAL FOR STRUCTURAL WINDOW MULLION |
| | 6-REVISE SHEET SH-1. GLASS BLOCK TO BE |
| | USED SHALL HAVE 2 HOUR FIRE RATING AT |
| | 2 HR WALL SEPARATION BET. TOWNHOUSES, |
| | NOT 3/4 HR. |
| | |
| | |
| | NOTES: |
| | -DRAWINGS TO BE FILED UNDER PERMIT # |
| | 01080506. |
| | -THESE COMMENTS APPLY TO PERMIT #S: |
| | 01080506, 01080498 AND 01080507. |