| Plan Review Notes For Permit 01080484 |
| Permit Number |
01080484 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-13 00:00:00 | *******************PROVISO************** | | | | | | | | | AHU 1 - NO ACCESS INDICATED ON PLAN. | | | ACCESS FOR ATTIC INSTALLATION SHALL | | | COMPLY WITH 1997 SMC 304.4.1 (ACCESS | | | OPENING SHALL BE NO LESS THAN 22" X | | | 36").ALL AIR CONDITIONING/HEATING | | | EQUIPMENT INSTALLED IN ATTIC SHALL HAVE | | | AN ACCESSIBLE DISCONNECT SWITCH AND A | | | 110-120 VOLT A/C GROUNDING TYPE | | | CONVENIENCE OUTLET. | | | | | | ALIGHT SHALL BE PROVIDED ON SERVICE | | | SIDE OF EQUIPMENT CONTROLLED BY A | | | SWITCH AT ATTIC OPENING. | | | | | | DRAIN PANS WITH OVERFLOW PROTECTION ALSO | | | REQUIRED AS PER 1997 SMC 304.8.6.1. | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|