| 2001-09-19 00:00:00 | TRUSS DRAWINGS CHECKLIST: |
| | 1-WHAT OFFICE REVIEWED THE TRUSS DWGS? |
| | STAMP USED DOESN'T IDENTIFY THE FIRM |
| | OR ENGINEER WHO REVIEWED THE DRAWINGS. |
| | 2-REVISE TRUSS GENERAL DETAILS AS REQ'D: |
| | A)ENGINEER TO PROVIDE ORIGINAL SIGNATURE |
| | AND DATE. CHAPTER 471 FL STATUTES. |
| | B)CLEARLY IDENTIFY THE DESIGN CRITERIA |
| | USED: SBC 1997 FOR 110MPH OR ASCE 7-95 |
| | FOR 145 MPH. |
| | C)UPDATE ALL GENERAL DETAILS AS REQUIRED |
| | USING ASCE 7-95 145MPH OR SBC 1997. |
| | |
| | 3-CLARIFY WHY THERE ARE TWO DIFFERENT |
| | ENGINEERS SIGNING AND SEALING THE |
| | ENGINEERED TRUSSES. NAMES OF THE |
| | ENGINEERS ARE SIMILAR BUT THEY HAVE |
| | DIFFERENT LICENSE NUMBER. |
| | -RESPONSIBLE ENGINEER TO PROVIDE THE |
| | ORIGINAL SIGNATURE, DATE AND SEAL AS |
| | REQUIRED BY CHAPTER 471 FL STATUTES. |
| | |
| | 4-TRUSS LAYOUT NEED ALL THE ENGINEER'S |
| | INFORMATION AS REQUIRED BY CHAPTER 471 |
| | OF FLORIDA STATUTES. |
| | -NOTE: MAKE SURE THAT ENGINEER IS THE |
| | SAME WHO IS SIGNING AND SEALING THE |
| | GENERAL DETAILS AND ENGINEERED TRUSS |
| | DRAWINGS. |
| | |
| | |
| | NOTES: |
| | -DRAWINGS TO BE FILED UNDER PERMIT # |
| | 01080463. |
| | -THESE COMMENTS APPLY TO PERMIT #S: |
| | 01080463, 01080466, 01080459, 01080455, |
| | 01080453 AND 01080451. |