| 2002-01-10 00:00:00 | ******** PROVISO /REVISION************ |
| | |
| | |
| | 1)NOTE: PLEASE NOTE, LOAD CALCULATIONS |
| | NEED TO BE REVISED. PLEASE SEE 220-3, |
| | 220-10,220-11,220-13. LIGHTING=WATTS/PER |
| | SQ FT.TRACK LIGHTING PER 220-12B 150VA |
| | PER 2' OF TRACK. |
| | PLEASE NOTE ALL CONTINUOUS LOADS TO BE |
| | SHOWN AT 125%.(LIGHTING) 215-3/230-42 |
| | OUTLETS PER 220-13 180VA PER OUTLET. |
| | |
| | 2)NOTE: PLEASE NOTE THAT CONDUCTORS |
| | FEEDING PANEL 3A ARE ONLY RATED FOR |
| | 100AMPS. PLEASE SEE 310-16 FOR CORRECT |
| | CONDUCTOR SIZING FOR 125A`S. IF 125A |
| | DISCONNECT OS FUSED DOWN? PLEASE SHOW. |
| | |
| | 3)NOTE: PLEASE NOTE THAT NOTE ON PLAN |
| | SHOWS CIRCUITS FOR THE TENANT SPACE |
| | TO BE CIRCUITED TO ELECTRICAL ROOM? |
| | PLEASE NOTE ALL OTHER TENANT SPACES HAVE |
| | THERE OWN ELECTRICAL PANEL,PLEASE NOTE |
| | EACH TENANT MUST HAVE ACCESS TO THEIR |
| | OWN PANEL/CIRCUITS IN ORDER TO TURN |
| | OFF IF NEEDED/OR IF SOMETHING TRIPPED, |
| | THEY WOULD BE ABLE TO RESET. PLEASE |
| | ALSO NOTE THAT ELECTRICAL ROOMS MUST |
| | BE ACCESSIBLE TO QUALIFIED PERSONNEL |
| | ONLY? PLEASE NOTE THAT A NEW PANEL IN |
| | SPACE WOULD MOST LIKELY BE REQUIRED. |
| | A BLDG UNDER SINGLE MANGAMENT CAN MEET |
| | THE REQUIREMENT AS LONG AS A "QUALIFIED" |
| | PERSON IS AVAILABLE DURING BUSINESS HOUR |
| | -S. PLEASE NOTE THAT A "QUALIFIED PERSON |
| | IS SOMEONE THAT HOLDS AN ELECTRICAL |
| | LICENSE OF SOMEKIND(JOURNEYMAN) ETC. |
| | PLEASE CALL TO GO OVER THIS. PER NEC |
| | REGULATIONS. |
| | |
| | PLEASE SUBMIT THE ABOVE REVISION FOR |
| | REVIEW BEFORE ANY ROUGH INSPECTION IS |
| | CALLED IN. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. IF A MEETING IS NEEDED TO |
| | GO OVER ANYTHING, PLEASE DO NOT HESITATE |
| | IN CONTACTING ME. |
| | |