| Plan Review Notes For Permit 01080403 |
| Permit Number |
01080403 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-24 00:00:00 | *******************DENIED*************** | | | | | | | | | 1.CFM DISTRIBUTION ON PLAN ADDS UP TO | | | 2200 CFM, WHEREAS A/C EQUIPMENT | | | SCHEDULE INDICATES UNIT CFM = 1850. | | | PLEASE CORRELATE SCHEDULE AND PLAN. | | | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO SUPERVISORY | | | SIGNAL AT A CONSTANTLY ATTENDED | | | LOCATION OR TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS. NFPA 90A | | | 4-4.4.2 OR 4-4.4.3. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|