| Plan Review Notes For Permit 01080403 |
| Permit Number |
01080403 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-21 00:00:00 | ************ UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT ALL EXITING | | | AND EMERGENCY LIGHTING NEEDS TO BE | | | SHOWN ON LAYOUT. PLEASE NOTE THAT SUITE | | | 301 EXISTINGSHOWS NEW WIRING? PLEASE | | | SHOW EM LIGHTING AND EXIT LTS. | | | | | | 2)NOTE: PLEASE NOTE THAT ALL BRANCH | | | CIRCUITING NEEDS TO BE SHOWN ON PLANS | | | INCLUDING LIGHTING. | | | | | | 3)NOTE: PLEASE CLARIFY MEANS OF EQUIP- | | | -MENT GROUNDING BETWEEN DISC AND PANEL. | | | 250-122 | | | | | | 4)NOTE: PLEASE SUBMIT THE AIC RATING FOR | | | NEW DISCONNECT ALSO. 110-9/215-5 | | | | | | 5)NOTE: PLEASE CLARIFY LOAD SHOWN FOR | | | SERVICE? LOAD SHOWN AT 85AMPS. 11,120/ | | | 240V. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. PLEASE NOTE THAT COMMENTS CAN | | | BE GONE OVER ON THE PHONE OR IN PERSON. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|