Plan Review Notes
Plan Review Notes For Permit 01080384
Permit Number 01080384
Review Stop P
Sequence Number 1
Notes
Date Text
2001-10-11 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) PLUMBING NOTES #13. AIR CHAMBERS DO
 NOT WORK AND SHOULD NOT BE INSTALLED.
 IF THEY ARE INSTALLED THEY SHALL COMPLY
 WITH SPC-94 SEC 607.8.3 AND BE RECHARG-
 ABLE AND ACCESSABLE. PAGE PO.1
 2) PAGE PO.1 DOMESTIC WATER ISOMETRIC.
 PLEASE COMPLY WITH MANUFACTURE INSTALL-
 ATION INSTRUCTIONS AND WH-PDI 201,
 PLACEMENT OF WATER HAMMER ARRESTORS NOT
 AT TOP OF DROP AS SHOWN. SEE ATTACHED
 SHEET.
 3) P2.1 CONDENSATE TO TERMINATE PER
 MODEL COUNTYWIDE AMENDMENTS TO SPC-94
 SEC 804.3 NOT INTO SANITARY. PLEASE
 SHOW PROPER DRAINAGE OF CONDENSATE.
 4) PAGE P2.1 BREAKROOM (#215) SINK TO
 COMPLY WITH FACBC-97 SEC 4.24 - HEIGTH
 SEC 4.24.2, KNEE CLEARANCE 4.24.3,
 CLEAR FLOOR SPACE 4.24.5 ECT. SHOW DE-
 TAILS.
 5) PAGE P2.1 DRINKING FOUNTAIN SHALL
 COMPLY WITH FACBC-97 SEC 4.1.3(10(A),
 PROVISIONS TO BE MADE FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377