| Plan Review Notes For Permit 01080384 |
| Permit Number |
01080384 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-10-11 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) PLUMBING NOTES #13. AIR CHAMBERS DO | | | NOT WORK AND SHOULD NOT BE INSTALLED. | | | IF THEY ARE INSTALLED THEY SHALL COMPLY | | | WITH SPC-94 SEC 607.8.3 AND BE RECHARG- | | | ABLE AND ACCESSABLE. PAGE PO.1 | | | 2) PAGE PO.1 DOMESTIC WATER ISOMETRIC. | | | PLEASE COMPLY WITH MANUFACTURE INSTALL- | | | ATION INSTRUCTIONS AND WH-PDI 201, | | | PLACEMENT OF WATER HAMMER ARRESTORS NOT | | | AT TOP OF DROP AS SHOWN. SEE ATTACHED | | | SHEET. | | | 3) P2.1 CONDENSATE TO TERMINATE PER | | | MODEL COUNTYWIDE AMENDMENTS TO SPC-94 | | | SEC 804.3 NOT INTO SANITARY. PLEASE | | | SHOW PROPER DRAINAGE OF CONDENSATE. | | | 4) PAGE P2.1 BREAKROOM (#215) SINK TO | | | COMPLY WITH FACBC-97 SEC 4.24 - HEIGTH | | | SEC 4.24.2, KNEE CLEARANCE 4.24.3, | | | CLEAR FLOOR SPACE 4.24.5 ECT. SHOW DE- | | | TAILS. | | | 5) PAGE P2.1 DRINKING FOUNTAIN SHALL | | | COMPLY WITH FACBC-97 SEC 4.1.3(10(A), | | | PROVISIONS TO BE MADE FOR THOSE WHO HAVE | | | DIFFICULTY BENDING OR STOOPING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT. 8377 |
|