| Plan Review Notes For Permit 01080384 |
| Permit Number |
01080384 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-14 00:00:00 | 1) WRONG BUILDING CODE REFERENCED ON | | | PLANS. SHOULD READ 1997 STANDARD | | | BUILDING CODE. | | | 2) CODE RESEARCH BOX INDICATES A | | | MAXIMUM TRAVEL DISTANCE OF 750 FEET. | | | THIS INFORMATION IS OBVIOUSLY AN ERROR. | | | 3) CLASS B, STYLE C FIRE ALARM CIRCUITS | | | NOTED IN FIRE ALARM NOTES IS NOT | | | CORRECT. ONLY CLASS A, STLE D ALLOWED. | | | 4) PLEASE INDICATE FIRE RATINGS FOR | | | DOORS 2,3,AND 6. | | | 5) PLEASE INDICATE EMERGENCY LIGHTS | | | IN TENANT HALLWAY. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|