| 2001-09-10 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01080384 | | | 326 FERN ST / 2ND FLOOR | | | "PLAN REVIEW" | | | QUINCY JOHNSON ARCHETECTS | | | TEL: (561) 997-9997 | | | FAX: (561) 997-1610 | | | | | | SBC= STANDARD BUILDING CODE 1997 EDI. | | | 1)- CODE RESEARCH GOVERNING CODE : | | | ADOPTED 1997 SBC | | | | | | 2)- TRAVEL DISTANCE: NOT 750', SBC | | | TABLE 1004 SPRINKLERED 250'. | | | | | | 3)- SBC TABLE 704.2.4 SPRINKLERED/ SEE | | | RATING FOR EXIT ACCESS CORRIDOR. | | | | | | 4)- SBC SEC.1020.1(2) 3500' > REQUIRE | | | 2 EXITS,1/2 THE DIAGONAL DISTANCE BE- | | | TWEEN THE 2 EGRESS DOORS.SEE 1004.1.4. | | | | | | 5)- THE SPACE TO THE RIGHT OF THIS TEN- | | | ANT SPACE WILL ALSO REQUIRE (2) EGRESS | | | DOORS @ 1/2 THE DIAGONAL DISTANCE BE- | | | TWEEN DOORS. | | | | | | | | | 6)-SBC 1020.2 LOCKING : A SIGN " THIS | | | EXIT TO REMAIN UNLOCKED WHEN THIS BUILD- | | | ING IS OCCUPIED. | | | | | | SBC 803.3 THE MINIMUM INTERIOR FINISH | | | CLASSIFICATION AS PER ASTM E 84. FLAME- | | | SPREAD & SMOKE DEVELOPMENT. | | | | | | PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X 8412 |
|