| Plan Review Notes For Permit 01080364 |
| Permit Number |
01080364 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-12 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) VARIANCE NOT APPROVED. SPC-97 NOT | | | ADOPTED IN PALM BEACH COUNTY. PLEASE | | | SUBMIT CALCULATIONS FOR MINIMUM FACILIT- | | | IES PER SPC-94 TABLE 407. | | | | | | 2) WATER HAMMER ARRESTORS TO BE PLACED | | | NEAR SOURCE NOT AT TOP OF DROPS PER | | | MANUFACTURES INSTALLATION INSTRUCTIONS | | | AND WH-PDI 201. | | | | | | 3) PAGE A.3 DOOR SHALL NOT OPEN INTO | | | CLEAR FLOOR SPACE PER FACBC-9 SEC 4.22.2 | | | DOORS TO HDCP BATHROOMS SHALL OPEN OUT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 569-8096 EXT. 8377 |
|