Plan Review Notes
Plan Review Notes For Permit 01080317
Permit Number 01080317
Review Stop B
Sequence Number 4
Notes
Date Text
2002-03-12 00:00:00BUILDING PLAN REVIEW
 PERMIT # 01080317
 213 S CONGRESS
  
 1997 SBC= STANDARD BUILDING CODE
  
 1) TRUSS SHOP DRAWINGS TO BE REVIEWED
 BY THE DESIGNER OF RECORD AND APPROVED
 BEFORE BUILDING DEPARTMENT REVIEW
  
 2) SHEET S-4 SECTION "A" INDICATES A 3
 POINT BEARING TRUSS, THE TRUSS DRAWINGS
 INDICATE A 2 POINT BEARING, THE LOADS
 ARE GREATER THAN ALLOWED,ONLY THE UPLIFT
 OF 160% CAN BE USED NOT THE AVERAGE
 ULTIMATE! SEE H16 FOR OVER THE TOP USE.
 SEE MGT SERIES FOR LARGER UPLIFTS.
  
 3) SHEETS4 INDICATES A STRAP "ETA12"
 NOT TO BE FOUND IN THE 2002 SIMPSON CATA
 LOG?
  
 4) SHEET S4 ALSO INDICATES A DETAIL "C"
 WITH THE USE OF A "H-10" , HOW WILL THE
 ANCHOR BE TAPCONED WITH A 4"X4" ANGLE
 IN FRONT OF IT?