| 2002-03-12 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 01080317 | | | 213 S CONGRESS | | | | | | 1997 SBC= STANDARD BUILDING CODE | | | | | | 1) TRUSS SHOP DRAWINGS TO BE REVIEWED | | | BY THE DESIGNER OF RECORD AND APPROVED | | | BEFORE BUILDING DEPARTMENT REVIEW | | | | | | 2) SHEET S-4 SECTION "A" INDICATES A 3 | | | POINT BEARING TRUSS, THE TRUSS DRAWINGS | | | INDICATE A 2 POINT BEARING, THE LOADS | | | ARE GREATER THAN ALLOWED,ONLY THE UPLIFT | | | OF 160% CAN BE USED NOT THE AVERAGE | | | ULTIMATE! SEE H16 FOR OVER THE TOP USE. | | | SEE MGT SERIES FOR LARGER UPLIFTS. | | | | | | 3) SHEETS4 INDICATES A STRAP "ETA12" | | | NOT TO BE FOUND IN THE 2002 SIMPSON CATA | | | LOG? | | | | | | 4) SHEET S4 ALSO INDICATES A DETAIL "C" | | | WITH THE USE OF A "H-10" , HOW WILL THE | | | ANCHOR BE TAPCONED WITH A 4"X4" ANGLE | | | IN FRONT OF IT? |
|