2 |
|
| Notes |
| Date |
Text |
| 2001-10-27 00:00:00 | PLUMBING PLAN REVIEW, DENIED. | | | PLEASE ADDRESS PREVIOUS NOTES 08-22-01 | | | (3) SHT P-1, REFERENCE TO AIR CHAMBERS, | | | PDI-WH 201,STATES AIR CHAMBERS ARE A | | | TEMPOARY FIX.USE WATER HAMMER ARRESTOR | | | PLACEMENT PER MFG INSTRUCTIONS, NOT AT | | | HIGH POINT OF SYSTEM, SPECIFY TYPE. | | | (5) SHT P-3 RM C-35 GWH, SAFE WASTE NOT | | | ALLOWED, SEC 1001.8 PLBG FIXTURES TO BE | | | SEPERATELY TRAPED. | | | (NEW COMMENT) SHT P-3,6" BUILDING DRAIN. | | | SEC 914,BUILDING DRAIN SHALL NOT PASS | | | THRU A BATTERY VENTED BRANCH. | | | ALSO TWO WAY CLEANOUT LOCATED 3' OUTSIDE | | | BUILDING, SEC 710.2 | | | PLEASE SUBMIT CIVIL PLANS, SHOWING ALL | | | SITE UTILITIES. | | | SEPERATE PLANS FOR GAS AND IRRIGATION | | | SIGNED AND SEALED AT TIME OF PERMIT. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|