Plan Review Notes
Plan Review Notes For Permit 01080317
Permit Number 01080317
Review Stop P
Sequence Number 2
Notes
Date Text
2001-10-27 00:00:00PLUMBING PLAN REVIEW, DENIED.
 PLEASE ADDRESS PREVIOUS NOTES 08-22-01
 (3) SHT P-1, REFERENCE TO AIR CHAMBERS,
 PDI-WH 201,STATES AIR CHAMBERS ARE A
 TEMPOARY FIX.USE WATER HAMMER ARRESTOR
 PLACEMENT PER MFG INSTRUCTIONS, NOT AT
 HIGH POINT OF SYSTEM, SPECIFY TYPE.
 (5) SHT P-3 RM C-35 GWH, SAFE WASTE NOT
 ALLOWED, SEC 1001.8 PLBG FIXTURES TO BE
 SEPERATELY TRAPED.
 (NEW COMMENT) SHT P-3,6" BUILDING DRAIN.
 SEC 914,BUILDING DRAIN SHALL NOT PASS
 THRU A BATTERY VENTED BRANCH.
 ALSO TWO WAY CLEANOUT LOCATED 3' OUTSIDE
 BUILDING, SEC 710.2
 PLEASE SUBMIT CIVIL PLANS, SHOWING ALL
 SITE UTILITIES.
 SEPERATE PLANS FOR GAS AND IRRIGATION
 SIGNED AND SEALED AT TIME OF PERMIT.
 END OF COMMENTSPAUL SCHMITZ