| 2001-08-22 00:00:00 | DENIED |
| | REFERENCE: SPC-94/FACBC-97 |
| | |
| | 1) PROVIDE AVERAGE DAILY ATTENDENCE FIG- |
| | URES FOR CLASSROOMS TO COMPUTE MINIMUM |
| | FACILITIES PER TABLE 407- SPC-94 |
| | |
| | 2) PAGE A12 WATER CLOSETS TO COMPLY WITH |
| | SECT. 4.16 - LAVS. TO COMPLY WITH 4.19 - |
| | URNALS TO COMPLY WITH 4.18 - SINKS TO |
| | COMPLY WITH 4.24 - FACBC-97. |
| | |
| | 3) PAGE P-1 GENERAL PLUMBING NOTES #12. |
| | AIR CHAMBERS SHALL COMPLY WITH SPC-94, |
| | 607.8.2 & 607.8.3 ACCESSABLE/RECHARGE- |
| | ABLE (PDI WH 201).-WATER HAMMER ARR- |
| | ESTORS SHALL BE INSTALLED PER MANUFACT- |
| | URES INSTALLATION INSTRUCTION. |
| | |
| | 4) PAGE P-2 SANITARY - DISHWASHER TO |
| | DRAIN INTO KITCHEN SINK TAIL PIECE. |
| | |
| | 5) PAGE P-3 ROOM C35 (LAUNDRY/JANITOR), |
| | HUB DRAIN NOT ALLOWED. RELIEF LINE TO |
| | RUN FULL SIZED OUTSIDE TO AN OBSERVABLE |
| | POINT OR TO A FLOOR SINK WITH TRAP PRIM- |
| | ER. (PAGE P-10 SHOWS SAME DETAIL) |
| | |
| | 6) PAGES P-3 & P-5, 6" SANITARY TO RUN |
| | TO 6 X 4 WYE AFTER 1ST BATHROOM. (C18) |
| | |
| | 7) PAGE P-10 WATER HEATER DETAIL. DI- |
| | ELECTRIC UNIONS NOT ALLOWED. |
| | |
| | 8) SEPARATE GAS PERMIT REQUIRED. SEE |
| | ATTACHED SHEET FOR GAS PERMIT APPLICAT- |
| | ION REQUIREMENTS. INFORMATION TO BE FILL |
| | ED OUT WHEN APPLYING FOR GAS PERMIT. |
| | |
| | 9) SEPARATE IRRIGATION PERMIT REQUIRED. |
| | PLUMBING CONTRACTOR TO PROVIDE VALVE AND |
| | ADAPTOR FOR IRRIGATION CONTRACTOR TO TIE |
| | INTO. |
| | |
| | 10) BACKFLOW REQUIRED FOR WATER SERVICE |
| | INTO NEW BUILDING. |
| | |