| Plan Review Notes For Permit 01080317 |
| Permit Number |
01080317 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-09 00:00:00 | ********************DENIED************** | | | | | | | | | 1.AHU-1 FOR THE BOARD ROOM DOES NOT | | | INDICATE A DUCT SMOKE DETECTOR. | | | | | | 2.PLAN M-5, EF #2 IS LESS THAN 10' | | | FROM RTU-5 AIR INTAKE. 1997 SMC | | | 506.1 STATES TERMINATION OF EXHAUST | | | OUTLETS SHALL BE A MINIMUM OF 10' | | | FROM FRESH AIR INTAKES ON 40" ABOVE | | | THE ROOF SURFACE. | | | | | | 3.PLAN M-6DETAIL OF CONDENSER UNIT | | | STAND, DOES NOT SPECIFY HEIGHT OF | | | STAND.AMENDED 1997 SMC 304.2.5 | | | REQUIRES A MINIMUM OF 18" FROM THE | | | ROOF SURFACE TO THE BOTTOM OF THE | | | SUPPORT RAIL. | | | | | | 4.PLEASE INDICATE CONDENSATE LINE | | | LINE SIZE, ROUTING AND TERMINATION | | | ON PLANS FOR REVIEW. | | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT. 8388. |
|