2001-08-09 00:00:00********************DENIED**************
  
  
 1.AHU-1 FOR THE BOARD ROOM DOES NOT
 INDICATE A DUCT SMOKE DETECTOR.
  
 2.PLAN M-5, EF #2 IS LESS THAN 10'
 FROM RTU-5 AIR INTAKE. 1997 SMC
 506.1 STATES TERMINATION OF EXHAUST
 OUTLETS SHALL BE A MINIMUM OF 10'
 FROM FRESH AIR INTAKES ON 40" ABOVE
 THE ROOF SURFACE.
  
 3.PLAN M-6DETAIL OF CONDENSER UNIT
 STAND, DOES NOT SPECIFY HEIGHT OF
 STAND.AMENDED 1997 SMC 304.2.5
 REQUIRES A MINIMUM OF 18" FROM THE
 ROOF SURFACE TO THE BOTTOM OF THE
 SUPPORT RAIL.
  
 4.PLEASE INDICATE CONDENSATE LINE
 LINE SIZE, ROUTING AND TERMINATION
 ON PLANS FOR REVIEW.
  
  