| Plan Review Notes For Permit 01080287 |
| Permit Number |
01080287 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-09-12 00:00:00 | *******************PROVISO************** | | | | | | | | | AUXILIARY DRAIN PAN SHALL HAVE MEANS OF | | | OVERFLOW PROTECTION BY A SEPARATE DRAIN | | | LINE EXENDED FROM PAN AND TERMINATING AT | | | A CONSPICUOUS POINT TO SERVE AS AN | | | ALARM THAT THE REGULAR DRAIN IS | | | RESTRICTED OR PROTECTION BY MEANS OF A | | | FLOAT SWITCH. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT | | | PATTY KRAUSS AT 659-8096 EXT 8388. |
|