| Plan Review Notes For Permit 01080287 |
| Permit Number |
01080287 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-08-08 00:00:00 | 1) BUILDING CODE ANALYSIS BOX INDICATES | | | 250 FEET FOR TRAVEL DISTANCE. THE | | | PREVAILING FIRE CODE ALLOWS 150 FEET | | | MAXIMUM IN SPRINKLER PROTECTED | | | MERCANTILE OCCUPANCIES. | | | 2) GENERAL NOTES INDICATES BUCKS COUNTY, | | | STATE OF PENNSYLVANIA. PROJECT IS | | | LOCATED IN PALM BEACH COUNTY, STATE OF | | | FLORIDA. | | | 3) PROVIDE SEPARATE PLANS AND PERMITS | | | FOR FIRE ALARM SYSTEM REMODEL. | | | 4) EXITING PERMITTED THRU STOCKROOM IF | | | THE FOLLOWING CONDITIONS EXIST: DOOR | | | TO STOCKROOM IS NOT LOCKED, AN AISLE OF | | | AT LEAST 44" WIDE IS PROVIDED AND | | | MAINTAINED. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|