| 2001-08-21 00:00:00 | **************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | IT IS SHOWN ON PANELS AS?? PLEASE NOTE |
| | RATINGS ARE REQ`D FOR ALL.215-5 |
| | |
| | 2)NOTE: PLEASE NOTE THAT UNDER CITY OF |
| | WEST PALM BEACH LOCAL AMENDMENTS, OUTLET |
| | SPACING AT EVERY 20' OF UNENCUMBERED |
| | WALL SPACE INCLUDING STORAGE/STOCK AREA. |
| | 210-50 |
| | 3)NOTE: PLEASE SUBMIT CLARIFICATION ON |
| | GROUNDING OF TRANSFORMER PER 250-30. |
| | |
| | 4)NOTE: PLEASE ALSO NOTE PER LOCAL |
| | AMENDMENTS, COLOR CODING OF 277/480V |
| | IS BROWN/PURPLE/YELLOW PER ART215 OF |
| | LOCAL AMEND. |
| | |
| | 5)NOTE: PLEASE NOTE THAT ALL CONTINUOUS] |
| | LOADS NEED TO BE SHOWN PER 215-3 AND |
| | 230-42. PLEASE ALSO NOTE THAT LOAD |
| | CALCUALTIONS NEED TO BE COMPLETED AND |
| | SHOWN. PER 215-5 |
| | |
| | 6)NOTE: PLEASE SEE A-0, PLEASE NOTE |
| | THAT PLANS REFERENCE THE 1996 NEC. |
| | PLEASE NOTE THAT WE ARE UNDER THE 99 NEC |
| | PLEASE ALSO NOTE THAT GENERAL NOTES ON |
| | SAME PAGE MENTION THAT ALL WORK TO |
| | COMPLY WITH "BUCKS COUNTY" PA. |
| | PLEASE CORRECT. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |