| Notes |
| Date |
Text |
| 2001-08-09 00:00:00 | 1) NO PORTIONS OF THE UNDERGOUND FIRE | | | LINES ARE TO BE RUN UNDERNEATH ANY | | | BUILDINGS. | | | 2) ALL UNDERGROUND FIRE LINES TO BE | | | PRESSURE TESTED FOR TWO HOURS. | | | 3) PLEASE INDICATE ANY AND ALL FIRE | | | HYDRANT LOCATIONS ON EAST AVENUE AND | | | LOCATED ON THE HOSPICE SITE. | | | 4) ELECTRONIC DEVICES REQUIRED ON | | | OS&Y VALVES. | | | 5) NEW UNDERGROUND FIRE LINES TO COMPLY | | | WITH NFPA 24, UTILITY AND FIRE RESCUE | | | REQUIREMENTS. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|