Plan Review Notes
Plan Review Notes For Permit 01080263
Permit Number 01080263
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-09 00:00:001) NO PORTIONS OF THE UNDERGOUND FIRE
 LINES ARE TO BE RUN UNDERNEATH ANY
 BUILDINGS.
 2) ALL UNDERGROUND FIRE LINES TO BE
 PRESSURE TESTED FOR TWO HOURS.
 3) PLEASE INDICATE ANY AND ALL FIRE
 HYDRANT LOCATIONS ON EAST AVENUE AND
 LOCATED ON THE HOSPICE SITE.
 4) ELECTRONIC DEVICES REQUIRED ON
 OS&Y VALVES.
 5) NEW UNDERGROUND FIRE LINES TO COMPLY
 WITH NFPA 24, UTILITY AND FIRE RESCUE
 REQUIREMENTS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910