Plan Review Notes
Plan Review Notes For Permit 01080263
Permit Number 01080263
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-08-08 00:00:00FAILED:
 1. PLEASE PROVIDE DETAILS FOR THE RIPRAP
 ENDWALL OR REFER TO FDOT STD. INDEX.
 2. PLEASE PROVIDE STOP BARS AT ALL NEW
 AND EXISTING DRIVEWAYS.
 3. PLEASE COORDINATE WITH PUBLIC
 UTILITIES ENGINEERING SERVICES REGARDING
 THE PROPOSED LIFT STATION AND ALL THE
 NEW CONNECTIONS TO CITY'S SERVICES, 659-
 8040.
 4. WE RECOMMEND TO LOCATE THE PROP. 3"
 DUAL REDUCED PRESSURE BACKFLOW PREVENTER
 ASSEMBLY AT THE CORNER NEXT TO THE 3"
 METER.ALL THE BACKFLOW PREVENTERS MUST
 BE HIDDEN FROM VIEW WITH SHRUBS.
 5. PLEASE STATE THE PURPOSE OF THE WATER
 METER AS MARKED ON SHEET C-2.
 6. PLEASE PROVIDE DETAILS FOR THE
 PROPOSED DUMPSTER.IT SHOULD BE
 DETAILED PER CITY'S REQUIREMENT IF TO BE
 PICKED UP BY THE CITY.
 7. PLEASE PROVIDE STORM WATER
 CALCULATIONS FOR OUR REVIEW.
 8. PLEASE PROVIDE PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR ENTIRE SITE.
 9. ALL UTILITIES THAT ARE ABANDONED MUST
 BE GROUTED AND PLUGGED.
 1O. ANY WORK WITHIN PUBLIC R.O.W WILL
 REQUIRE A SEPARATE PERMIT FROM CITY'S
 ENGINEER OFFICE, 659-8040.
 11. PLEASE CALL RODNEY COMPO, INDUSTRIAL
 PRETREATMENT INSPECTOR FOR INSTALLATION
 AND OR INSPECTION OF THE PROP. GREASE
 TRAP, 837-4051EXT. 4074.
 12. CITY STD. AND DETAILS MAY BE
 OBTAINED FROM PUBLIC UTILITIES
 ENGINEERING SERVICES DEPARTMENT 659-8040
  
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI