2002-07-20 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT P-4 GAS RISER DIAGRAM, MANUAL
 SHUT OFF VALVE SHALL BE NEXT TO UNION
 AND AUTOMATIC SHUT OFF VALVE NOT APPROX.
 15' AS SHOWN.
  
 2) SHT SHT P-11 PLEASE SHOW TYPE OF PIPE
 INSTALLED UNDERGROUND.
  
 3) SHT P-11 SHOWS 3" SCHED 40 PIPE SUPP-
 LYING 1,670,000 @ 520 FEET. MAX IS
 1,514,000 BTU,S. MINIMUM 4" PIPE SHALL
 RUN FROM METER TO EXISTING GAS LINE FOR
 EXISTING HEATER.
  