| Plan Review Notes For Permit 01080260 |
| Permit Number |
01080260 |
|
| Review Stop |
P |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2002-07-20 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FACBC-97 | | | | | | 1) SHT P-4 GAS RISER DIAGRAM, MANUAL | | | SHUT OFF VALVE SHALL BE NEXT TO UNION | | | AND AUTOMATIC SHUT OFF VALVE NOT APPROX. | | | 15' AS SHOWN. | | | | | | 2) SHT SHT P-11 PLEASE SHOW TYPE OF PIPE | | | INSTALLED UNDERGROUND. | | | | | | 3) SHT P-11 SHOWS 3" SCHED 40 PIPE SUPP- | | | LYING 1,670,000 @ 520 FEET. MAX IS | | | 1,514,000 BTU,S. MINIMUM 4" PIPE SHALL | | | RUN FROM METER TO EXISTING GAS LINE FOR | | | EXISTING HEATER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|