Plan Review Notes
Plan Review Notes For Permit 01080260
Permit Number 01080260
Review Stop E
Sequence Number 6
Notes
Date Text
2002-02-05 00:00:00***************** UNSAT ***************
  
 PLEASE NOTE THAT PLANS ARE BACK IN FOR
 REVIEW. AS PER CONVERSATIONS ON PHONE
 WITH ENGINEER ALL MAINS WERE SAID TO BE
 GROUPED AND THE ONLY ISSUE WAS TO
 CLARIFY DOORS IN MAIN ELECTRICAL ROOM.
  
 1)NOTE: PLEASE NOTE "MAIN" FOR EMDP IS
 SHOWN BEING IN GENERATOR ROOM. PLEASE
 NOTE THE MAIN COMING FROM NORMAL FPL
 POWER IS LOCATED IN MAIN ELEC ROOM. THIS
 IS FINE, BUT WHEN SYSTEM LOSES NORMAL
 POWER AND GENERATOR KICKS IN, THE POWER
 FROM GEN GOES DIRECTLY TO EMDP AND
 THROUGHOUT EM PANELS. PLEASE NOTE, MAINS
 ARE STILL NOTE GROUPED PER 230-72.
 ALL EM PANELS WOULD BE "HOT" EVEN AFTER
 SHUTTING DOWN MAINS.
 WHATEVER HAPPENED TO SERVICE COMING INTO
 NEW ELECTRICAL/GENERATOR ROOM AND THEN
 FEEDING EXISTING BLDG?
 PLEASE NOTE 230-76/230-79
 PLEASE ALSO NOTE "EMDO " IS SHOWN AS
 "MLO"? PLEASE NOTE THAT MAIN ON GEN.
 MUST BE ON OUTSIDE OF UNIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372