| Notes |
| Date |
Text |
| 2002-02-05 00:00:00 | ***************** UNSAT *************** | | | | | | PLEASE NOTE THAT PLANS ARE BACK IN FOR | | | REVIEW. AS PER CONVERSATIONS ON PHONE | | | WITH ENGINEER ALL MAINS WERE SAID TO BE | | | GROUPED AND THE ONLY ISSUE WAS TO | | | CLARIFY DOORS IN MAIN ELECTRICAL ROOM. | | | | | | 1)NOTE: PLEASE NOTE "MAIN" FOR EMDP IS | | | SHOWN BEING IN GENERATOR ROOM. PLEASE | | | NOTE THE MAIN COMING FROM NORMAL FPL | | | POWER IS LOCATED IN MAIN ELEC ROOM. THIS | | | IS FINE, BUT WHEN SYSTEM LOSES NORMAL | | | POWER AND GENERATOR KICKS IN, THE POWER | | | FROM GEN GOES DIRECTLY TO EMDP AND | | | THROUGHOUT EM PANELS. PLEASE NOTE, MAINS | | | ARE STILL NOTE GROUPED PER 230-72. | | | ALL EM PANELS WOULD BE "HOT" EVEN AFTER | | | SHUTTING DOWN MAINS. | | | WHATEVER HAPPENED TO SERVICE COMING INTO | | | NEW ELECTRICAL/GENERATOR ROOM AND THEN | | | FEEDING EXISTING BLDG? | | | PLEASE NOTE 230-76/230-79 | | | PLEASE ALSO NOTE "EMDO " IS SHOWN AS | | | "MLO"? PLEASE NOTE THAT MAIN ON GEN. | | | MUST BE ON OUTSIDE OF UNIT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|