Notes
Date Text
2001-12-31 00:00:00****************** UNSAT ************
  
 1)NOTE: PLEASE NOTE, PLANS ARE NOW
 MOVING TWO OF THE THREE MAINS BACK TO
 ORIG ELECTRICAL ROOM? PLEASE CLARIFY
 HOW THE MAINS ARE NOW GROUPED PER 230-72
 ??
 PLEASE NOTE THAT THIS WAS AN ISSUE
 BEFORE AND PLANS WERE CORRECTED, WHY
 IS THIS BEING CHANGED BACK TO THE SAME
 COMMENTS AS BEFORE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  