| Plan Review Notes For Permit 01080260 |
| Permit Number |
01080260 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-11-03 00:00:00 | DENIED | | | REFERENCE: SPC-94 - SGC-97 - FABCB-97 | | | 1) PERMIT WILL NOT BE ISSUED UNTIL THE | | | LETTER FROM PALM BEACH COUNTY HEALTH | | | UNIT DIVISION OF ENVIRONMENTAL HEALTH IS | | | RECIEVED FOR PLAN REVIEW AS REQUESTED. | | | 2) PAGE P-7 WATER RISER DIAGRAM. WATER | | | HAMMER ARRESTORS IN KITCHEN AREA AND IN | | | PUBLIC RESTROOMS (HOT) ARE REQUIRED TO | | | BE CLOSE TO FIXTURES NOT AT TOP OF DROP | | | AS SHOWN. PLEASE COMPLY | | | 3) PAGE P-10 HUMIDIFIER DETAIL. FLOOR | | | DRAIN TO BE CHANGED TO FLOOR SINK AS RE- | | | QUESTED IN PREVIOUS COMMENTS. | | | 4) LETTER FROM RODNEY COMPO STILL NOT | | | RECIEVED. LETTER REQUIRED FOR SIZING & | | | LOCATING GREASE TRAP. | | | 5) PAGE A-11 HDCP SHOWER DETAIL. NEW DE- | | | TAIL ADD IN FOR 60" SHOWER. HDCP SHOWERS | | | SHOWN ARE NOT 60" SHOWERS AND SHALL COM- | | | PLY WITH FIGURE 35(A) FACBC-97. PLEASE | | | SHOW COMPLIANCE WITH SEC 4.21. | | | 6) PLEASE SUBMIT CALCULATION FOR CONFIN- | | | ED SPACE FOR WATER HEATERS. RESPONSE | | | SHOWS VENTING BY NOT CALCULATIONS FOR | | | COMBUSTION AIR. LOUVERS SHOWN ON PAGE | | | A-5 ARE NOT A LARGE ENOUGH AREA FOR | | | EITHER ROOM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|