| Plan Review Notes For Permit 01080260 |
| Permit Number |
01080260 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-11-07 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE AS PER LAST | | | CONVERSATION, EITHER SERVICE WAS GOING | | | TO BE GROUPED AND CIRCUITS BE ZONED SO | | | NOT TO CROSS EXISTING WITH NEW, OR | | | A NEW SERVICE LARGE ENOUGH TO BACK FEED | | | EXISTING? | | | PLEASE NOTE: 230-2 /230-72 | | | | | | 2)NOTE: PLEASE NOTE THAT SHUNT TRIPS | | | ARE NOT RATED FOR PURPOSE SHOWN. NEEDS | | | TO MEET 230-76 AND 230-79. | | | | | | | | | PLEASE CALL TO SET UP A MEETING TO GO | | | OVER ELECTRICAL SERVICE AND REQ`MENTS | | | FOR PROJECT. PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | | | | JAKE LEAHY | | | CHIEF ELECTRICAL INSPECTOR | | | 561-659-8096 EXT 8451 |
|