Plan Review Notes For Permit 01080260
Permit Number 01080260
Review Stop B
Sequence Number 3
Notes
Date Text
2001-11-27 00:00:00 
  
  
  
 THE FIRE PROTECTION PLANS ARE REQUIRED
 TO BE SIGNED AND SEALED
  
 IF SOMEONE HAS NOT SPECIFICALLY
 REQUESTED THAT "VOID" PAGES BE RETAINED
 IN THE PLANS AND SPECIFICTIONS, I
 SUGGEST THAT THEY BE REMOVED AS THEY
 ARE A SOURCE OF CONFUSION AND CLUTTER.
  
 SHEET LS-1 DATED 10/4/01 SHOWS A SMOKE
 BARRIER ALONG GRID LINE L AT THE
 EXISTING BUILDING.WILL THE TWO
 PROPOSED WINGS ON THE NORTH END SHOWN
 WITH "RESIDENTIAL ROOMS" BE REQUIRED TO
 TRAVEL TO THAT BEGINS NEAR GRID A AND
 4?WHAT IS THE DISTANCE?SEE SBC
 409.1.2.1.