| Date |
Text |
| 2001-10-09 00:00:00 | DENIED |
| | REFERENCE: SPC-94 - FACBC-97 - SGC-97 |
| | |
| | NOTE: LETTER FROM PALM BEACH COUNTY |
| | HEALTH UNIT DIVISION OF ENVIRONMENTAL |
| | REQUIRED FOR PERMIT PLAN REVIEW. |
| | |
| | 1) PLEASE PROVIDE A WATER RISER DIAGRAM |
| | FOR PLAN REVIEW. SHOW SIZE AND LOCATION |
| | OF WATER HAMMER ARRESTORS PER MANUFACT- |
| | URE INSTALLATION INSTRUCTION AND WH-PDI |
| | 201. |
| | 2) STORM RISER DIAGRAM STILL REQUIRED |
| | FOR ROOF DRAINS AND SECONDARY DRAINS |
| | FOR ROOF ABOVE KITCHEN AND ADJOINING NEW |
| | ROOFS AND FOR ROOFS ABOVE NEW RESIDENT- |
| | IAL AREAS. SUBMIT CALCULATIONS FOR ROOF |
| | DRAINS AND SECONDARY DRAINS. SHOW ALL |
| | PIPE SIZES. |
| | 3) PAGE P-10 HUMIDIFIER DETAIL SHOWS THE |
| | INDIRECT WASTE TO FLOOR DRAIN. FLOOR |
| | SINK IS REQUIRED, PLEASE CHANGE DETAIL. |
| | 4) LETTER FROM R. COMPO REQUIRED FOR |
| | GREASE TRAP SIZING AND LOCATION. PLEASE |
| | HAVE INFORMATION FOR PLAN REVIEW. (FROM |
| | PREVIOUS REVIEW ITEM #6.) |
| | 5) PAGE A-11 HDCP SHOWER DETAIL. PLEASE |
| | SHOW ALL DETAILS REQUESTED ON PREVIOUS |
| | PLAN REVIEW. SEAT, CURB TO BE 1/2" PER |
| | FACBC-97. AND SEC 6 BACKING. |
| | 6) MY PREVIOUS COMMENTS #12 NOT ADDRESS- |
| | ED FOR DIRECT VENT FOR WATER HEATER. |
| | PLEASE PROVIDE DETAILS. |
| | 7) ALL CONDENSATE TO DRAIN SEPARATE FROM |
| | BLDG. PLEASE PROVIDE CONDENSATE RISER |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT. 8377 |