Plan Review Notes
Plan Review Notes For Permit 01080260
Permit Number 01080260
Review Stop P
Sequence Number 2
Notes
Date Text
2001-10-09 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97 - SGC-97
  
 NOTE: LETTER FROM PALM BEACH COUNTY
 HEALTH UNIT DIVISION OF ENVIRONMENTAL
 REQUIRED FOR PERMIT PLAN REVIEW.
  
 1) PLEASE PROVIDE A WATER RISER DIAGRAM
 FOR PLAN REVIEW. SHOW SIZE AND LOCATION
 OF WATER HAMMER ARRESTORS PER MANUFACT-
 URE INSTALLATION INSTRUCTION AND WH-PDI
 201.
 2) STORM RISER DIAGRAM STILL REQUIRED
 FOR ROOF DRAINS AND SECONDARY DRAINS
 FOR ROOF ABOVE KITCHEN AND ADJOINING NEW
 ROOFS AND FOR ROOFS ABOVE NEW RESIDENT-
 IAL AREAS. SUBMIT CALCULATIONS FOR ROOF
 DRAINS AND SECONDARY DRAINS. SHOW ALL
 PIPE SIZES.
 3) PAGE P-10 HUMIDIFIER DETAIL SHOWS THE
 INDIRECT WASTE TO FLOOR DRAIN. FLOOR
 SINK IS REQUIRED, PLEASE CHANGE DETAIL.
 4) LETTER FROM R. COMPO REQUIRED FOR
 GREASE TRAP SIZING AND LOCATION. PLEASE
 HAVE INFORMATION FOR PLAN REVIEW. (FROM
 PREVIOUS REVIEW ITEM #6.)
 5) PAGE A-11 HDCP SHOWER DETAIL. PLEASE
 SHOW ALL DETAILS REQUESTED ON PREVIOUS
 PLAN REVIEW. SEAT, CURB TO BE 1/2" PER
 FACBC-97. AND SEC 6 BACKING.
 6) MY PREVIOUS COMMENTS #12 NOT ADDRESS-
 ED FOR DIRECT VENT FOR WATER HEATER.
 PLEASE PROVIDE DETAILS.
 7) ALL CONDENSATE TO DRAIN SEPARATE FROM
 BLDG. PLEASE PROVIDE CONDENSATE RISER
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT. 8377