Plan Review Notes For Permit 01080260
Permit Number 01080260
Review Stop M
Sequence Number 2
Notes
Date Text
2001-10-12 00:00:00*******************DENIED***************
  
 1.FIRE DAMPERS REQUIRED FOR ROOM 186,
 PENETRATION THRU 3 HR WALL.ALSO
 ON PLAN SHEET M-5, ROOMS 241 AND
 237 REQUIRE FIRE DAMPERS.
  
 2.SMOKE DAMPERS REQUIRED FOR DUCTS
 PENETRATING SMOKE WALLS IN THE
 RESIDENTIAL AREAS (PLAN SHEET M-3).
 1997 SMC 610.3.1.
  
 3.AUXILIARY DRAIN PANS REQUIRED WITH
 OVERFLOW PROTECTION FOR FAN COIL
 UNITS.1997 SMC 304.8.6.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.