| 2001-10-12 00:00:00 | *******************DENIED*************** | | | | | | 1.FIRE DAMPERS REQUIRED FOR ROOM 186, | | | PENETRATION THRU 3 HR WALL.ALSO | | | ON PLAN SHEET M-5, ROOMS 241 AND | | | 237 REQUIRE FIRE DAMPERS. | | | | | | 2.SMOKE DAMPERS REQUIRED FOR DUCTS | | | PENETRATING SMOKE WALLS IN THE | | | RESIDENTIAL AREAS (PLAN SHEET M-3). | | | 1997 SMC 610.3.1. | | | | | | 3.AUXILIARY DRAIN PANS REQUIRED WITH | | | OVERFLOW PROTECTION FOR FAN COIL | | | UNITS.1997 SMC 304.8.6.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|