| Plan Review Notes For Permit 01080260 |
| Permit Number |
01080260 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-09 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SHOW HOW NEW SERVICE | | | CIRCUITS ARE GOING TO BE"ZONED" FROM | | | EXISTING CIRCUITS? RISER SHOWS NEW | | | SERVICE FEEDING EXISTING PANELS IN THE | | | EXISTING BLDG. | | | IS IS NOTED ON THIS PLAN REVIEW, THAT | | | THE NEW AND OLD SERVICE IS NOT GROUPED, | | | THIS WILL BE ALLOWED DUE TO THE SIZE OF | | | THE EXISTING SERVICE AND BLDG AS LONG | | | AS SERVICES ARE LABELED WITH THE | | | PLAGUESTHAT ARE NOTED ON PLANS. | | | PLEASE SHOW HOW NEW AND OLD CIRCUITS | | | AREGOING TO BE SEPARATED. | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | THIS WAS SUBMITTED TO THE CHIEF | | | ELECTRICAL INSPECTOR FOR REVIEW AND | | | "ZONING" | | | CLARIFICATIONS NEEDS TO BE SUBMITTED. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | JAKE LEAHY | | | CHIEF ELECTRICAL INSPECTOR | | | 561-659-8096 EXT 8451 |
|