| Plan Review Notes For Permit 01080260 |
| Permit Number |
01080260 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-10-16 00:00:00 | THE FIRE SPRINKLER PROTECTION SYSTEM | | | DESIGN IS REQUIRED BY FS 553.79 (2) TO | | | BE SUBMITTED WITH THE PERMIT PLANS. | | | | | | THE SPECIFICATIONS BOOKS WERE RETURNED | | | MARKED VOID AND WERE NOT REVIEWED. | | | PROVIDE THREE COPIES OF SIGNED, SEALED | | | AND DATED SPECIFICATIONS SO THAT CODE | | | COMPLIANCE MAY BE DETERMINED. | | | | | | SHEET S1 STILL HAS NOTES LIKE "LATEST | | | EDITION"SEE SBC 3502. | | | | | | THE ROOM SHOWN AS "SOILED UTILITY" IS | | | THAT A SOILED LINEN ROOM?SEE SBC | | | 409.1.2.3. | | | | | | LS1 NOW SHOWS A SMOKE BARRIER NEAR GRID | | | LINE A.IT APPEARS THAT THERE ARE | | | NEITHR PATIENT TREATMENT OR SLEEPING | | | FACILI | | | TIES IN THE AREA CONTAINED IN GRID A - L | | | AND IN THE EXISTING PATIENT AREA THE | | | DISTANCE WOULD EXCEED THE 200' TRAVEL | | | DISTANCE ALLOWED BY SBC 409.1.2.1. | | | PLEASE CLARIFY THE DESIGN INTENT. | | | LARIFY THE DESIGN INTENT. | | | | | | SEE THE 8/31/01 NOTES RE: IMPACT FEES, | | | RESIDENT INSPECTOR, AND PRODUCT/TEST | | | REPORTS. |
|