2001-08-27 00:00:00*******************DENIED***************
  
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW.
  
 1.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS AS PER ASHRAE 62-89.
  
 2.PROVIDE AIR BALANCE SCHEDULE TO
 SHOW COMPLIANCE WITH 1997 SMC 501.2
  
 3.FIRE DAMPERS NOT INDICATED ON PLAN
 FOR THE FOLLOWING ROOMS - 111, 126,
 168.
  
 4.INDICATE MAKE-UP AIR FOR GAS FIRED
 WATER HEATERS.
  
  
 NOTE:EXHAUST DUCTS CONVEYING NOXIOUS
 GASES, FLAMMABLE/CORROSIVE VAPORS
 AND DUCTS SERVING COMMERCIAL FOOD
 COOKING AND PROCESSING EQUIPMENT
 SHALL TERMINATE OUTSIDE OF THE
 BUILDING AND LOCATED 10' FROM ANY
 ADJACENT BUILDING, PARKING AREA,
 ADJACENT PROPERTY LINE, WINDOW,
 DOOR OR AIR INTAKE AND AT LEAST
 10' ABOVE THE ADJOINING GRADE
 LEVEL.EXHAUST OUTLET WHICH IS
 LOCATED ABOVE THE ROOF SHALL
 TERMINATE AT LEAST 40" ABOVE THE
 ROOF SURFACE.
  
 ADDITIONAL PLANS AND PERMITS REQUIRED
 FOR HOOD, FIRE SUPRESSION, AND WALK-IN
 COOLERS.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 PATTY KRAUSS AT 659-8096 EXT. 8388.