| 2001-08-27 00:00:00 | 1) HOW IS FIRE ACCESS PROPOSED TO THE |
| | RESIDENCE ROOMS AND FUTURE TWO-STORY |
| | FUTURE EXPANSION. |
| | 2) FIRE PROTECTION NOTE ON LS-1 |
| | INDICATES ROOM 161 WILL BE PROTECTED |
| | BY AN FM 200 SYSTEM. FM 200 SYSTEM |
| | CANNOT BE USED IN LIEU OF FIRE |
| | SPRINKLERS. |
| | 3) TABLE AND CHAIRS LOCATED DIRECTLY |
| | IN FRONT OF SINGLE EXIT DOORS IN STAFF |
| | DINING 2151. |
| | 4) PLEASE EXPLAIN ROLL-DOWN NOTE ON |
| | PAGE LS-1, PATIENT RECEPTION 464, NEAR |
| | EXIT DOOR. |
| | 5) PLEASE EXPLAIN FUTURE THERMAL STORAGE |
| | AREA, ON PAGE LS-1, WHAT IS THIS USED |
| | FOR. |
| | 6) PLEASE PROVIDE MORE DETAILS ON |
| | EMERGENCY GENERATOR. IF EMERGENCY |
| | GENERATOR IS DIESEL FUEL SUPPLIED, IT |
| | MUST BE AT LEAST AT LEAST TWO-HOUR |
| | RATED. |
| | 7) AUTOMOBILE PARKING GARAGE SHALL BE |
| | SEPARATED BY AT LEAST A TWO HOUR FIRE |
| | RATING NOT A ONE HOUR AS NOTED IN THE |
| | FIRE RESISTANCE SEPARATION NOTES ON |
| | PAGE LS-1. |
| | 8) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR ANY NEW HOOD,DUCT,AND SUPPRESSION |
| | SYSTEMS PLANNED FOR KITCHEN 700. |
| | 9) DEMOLITION ACTIVITIES PLANNED SHALL |
| | NOT INTERFERE WITH ANY EXIT ACCESS, |
| | EXITING, OR EXIT DISCHARGE. |
| | 10) IS THE EXISTING LIQUID OXYGEN TANK |
| | EXISTING OR NEW. HOW DOES THIS TANK |
| | AND APPURTENANT EQUIPMENT INTERFERE |
| | WITH ANY EXITING FROM THE CORRIDOR. |
| | 11) PLEASE INDICATE EXIT CAPACITY FOR |
| | STAIR 159. THIS STAIR APPEARS TO |
| | PROVIDE EXITING FOR THE GARAGE AND |
| | BUILDING. |
| | 12) CANVAS CANOPIES TO BE FIRE |
| | RETARDANT. |
| | 13) FOLDING PARTITION WHEN USED IN STAFF |
| | DINING 138 LIMITS ACCESS TO EXIT DOOR |
| | 138A. |
| | 14) PLEASE INDICATE OCCUPANT LOADS FOR |
| | TRAINING ROOM 200 AND 200A. |
| | 15) NO EXIT SIGNS DISPLAYED IN TRAINING |
| | ROOM 200 AND 200A. |
| | 16) SINGLE MEANS OF EGRESS PROVIDED FROM |
| | CLERICAL 214. PLEASE EXPLAIN. |
| | 17) FULL OXYGEN CYLINDERS SHOULD NOT |
| | BE STORED WITH EMPTY OXYGEN CYLINDERS |
| | IN 02 STORAGE G101. WHAT SAFETY |
| | PRECAUTIONS ARE PLANNED FOR 02 ROOM |
| | G101. |
| | 18) NO FIRE SPRINKLER OR HYDRAULIC |
| | CALCULATIONS PROVIDED WITH PLANS. |
| | 19) PLEASE INDICATE ON PLANS THAT |
| | GARAGE IS CONSIDERED OPEN AND DOCUMENT |
| | PERCENTAGE OF OPENINGS. |
| | |
| | MIKE CARSILLO, CAPTAIN |
| | 659-8096,EXT.8497 |
| | 835-2910 |