Plan Review Notes
Plan Review Notes For Permit 01080260
Permit Number 01080260
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-08-27 00:00:001) HOW IS FIRE ACCESS PROPOSED TO THE
 RESIDENCE ROOMS AND FUTURE TWO-STORY
 FUTURE EXPANSION.
 2) FIRE PROTECTION NOTE ON LS-1
 INDICATES ROOM 161 WILL BE PROTECTED
 BY AN FM 200 SYSTEM. FM 200 SYSTEM
 CANNOT BE USED IN LIEU OF FIRE
 SPRINKLERS.
 3) TABLE AND CHAIRS LOCATED DIRECTLY
 IN FRONT OF SINGLE EXIT DOORS IN STAFF
 DINING 2151.
 4) PLEASE EXPLAIN ROLL-DOWN NOTE ON
 PAGE LS-1, PATIENT RECEPTION 464, NEAR
 EXIT DOOR.
 5) PLEASE EXPLAIN FUTURE THERMAL STORAGE
 AREA, ON PAGE LS-1, WHAT IS THIS USED
 FOR.
 6) PLEASE PROVIDE MORE DETAILS ON
 EMERGENCY GENERATOR. IF EMERGENCY
 GENERATOR IS DIESEL FUEL SUPPLIED, IT
 MUST BE AT LEAST AT LEAST TWO-HOUR
 RATED.
 7) AUTOMOBILE PARKING GARAGE SHALL BE
 SEPARATED BY AT LEAST A TWO HOUR FIRE
 RATING NOT A ONE HOUR AS NOTED IN THE
 FIRE RESISTANCE SEPARATION NOTES ON
 PAGE LS-1.
 8) SEPARATE PLANS AND PERMITS REQUIRED
 FOR ANY NEW HOOD,DUCT,AND SUPPRESSION
 SYSTEMS PLANNED FOR KITCHEN 700.
 9) DEMOLITION ACTIVITIES PLANNED SHALL
 NOT INTERFERE WITH ANY EXIT ACCESS,
 EXITING, OR EXIT DISCHARGE.
 10) IS THE EXISTING LIQUID OXYGEN TANK
 EXISTING OR NEW. HOW DOES THIS TANK
 AND APPURTENANT EQUIPMENT INTERFERE
 WITH ANY EXITING FROM THE CORRIDOR.
 11) PLEASE INDICATE EXIT CAPACITY FOR
 STAIR 159. THIS STAIR APPEARS TO
 PROVIDE EXITING FOR THE GARAGE AND
 BUILDING.
 12) CANVAS CANOPIES TO BE FIRE
 RETARDANT.
 13) FOLDING PARTITION WHEN USED IN STAFF
 DINING 138 LIMITS ACCESS TO EXIT DOOR
 138A.
 14) PLEASE INDICATE OCCUPANT LOADS FOR
 TRAINING ROOM 200 AND 200A.
 15) NO EXIT SIGNS DISPLAYED IN TRAINING
 ROOM 200 AND 200A.
 16) SINGLE MEANS OF EGRESS PROVIDED FROM
 CLERICAL 214. PLEASE EXPLAIN.
 17) FULL OXYGEN CYLINDERS SHOULD NOT
 BE STORED WITH EMPTY OXYGEN CYLINDERS
 IN 02 STORAGE G101. WHAT SAFETY
 PRECAUTIONS ARE PLANNED FOR 02 ROOM
 G101.
 18) NO FIRE SPRINKLER OR HYDRAULIC
 CALCULATIONS PROVIDED WITH PLANS.
 19) PLEASE INDICATE ON PLANS THAT
 GARAGE IS CONSIDERED OPEN AND DOCUMENT
 PERCENTAGE OF OPENINGS.
  
 MIKE CARSILLO, CAPTAIN
 659-8096,EXT.8497
 835-2910